How To Configure The System - Danfoss VLT FC 100 Series Manual

Devicenet
Hide thumbs Also See for VLT FC 100 Series:
Table of Contents

Advertisement

FC 100/ 200/ 300 DeviceNet

3. How to Configure the System

3.1. Configure the DeviceNet Network
All DeviceNet stations that are connected to
the same bus network must have a unique
station address. The DeviceNet address of the
frequency converter can be selected via:
-
-
-
3.1.1. Setting the DeviceNet Address using the Hardware Switches
Setting the DeviceNet Address using the Hardware Switches: Using the hardware switches it is
possible to select an address range from 0-63 (factory setting 63) according to the table below:
Switch
Address value
Ex. address 5
Ex. address 20
Ex. address 35
The address change will come into effect at the next power-up, and can be read in par. 10-02
MAC ID
3.1.2. Setting the DeviceNet Address via Par. 10-02
The address can be set via par. 10-02
setting). The address change will come into effect at the next power-up.
3.1.3. Setting the DeviceNet Address with the Object Class Code
0x03, Attribute 1, Instance 1
The address can be set via the DeviceNet object class code 0x03 attribute 1 command if the
hardware switch is set to 63 (factory setting). A new address becomes effective immediately after
the class code 0x03, Instance 1, Attribute 1 command.
Hardware switches (default 63)
MAC ID
Parameter 10-02
63)
Class code 0X03, Instance 1, Attrib-
ute 1
8
7
-
-
-
-
-
-
-
-
NB!
Switch off the power supply before changing the hardware switches.
.
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
3. How to Configure the System
(default
6
5
4
+32
+16
+8
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
MAC ID
if the hardware switches are set to 63 (factory
3
2
1
+4
+2
+1
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
MAC ID