walk Through zones are isolated during the Entry Time. This gives users access to a
keypad or keyswitch.
If a Walk Through zone is activated while the system is Full Set it causes a full alarm.
5 — 24 Hour Tamper
The 24 Hour Tamper zone type is used for system/module tampers and for zones
covering sensitive areas such as stock rooms, fire doors, external bell box, etc.
If a 24 Hour Tamper zone is activated while the system is Unset the keypads sound
and the corresponding zone LED on the keypad illuminates, the external sounders
do not operate.
It is strongly recommended that a zone programmed as 24 Hour Tamper is pro-
grammed in one of the following ways:
• Programmed as 24 Hour Tamper in Groups 1 (Full Set), 2 (Part Set) and 3
(Night Set).
• Programmed as 24 Hour Tamper in Group 1 (Full Set), and, 0 (Not Used) or
24 Hour Tamper in Groups 2 (Part Set) and 3 (Night Set).
The programming of a zone in Group 1 (Full Set) also covers the unset condition.
7 — PA Audible
The PA Audible zone type is assigned to a Panic Button and will initiate a full alarm
condition.
It is strongly recommended that a zone programmed as PA Audible is programmed
in one of the following ways:
• Programmed as PA Audible in Groups 1 (Full Set), 2 (Part Set) and 3 (Night
Set).
• Programmed as PA Audible in Group 1 (Full Set), and, 0 (Not Used) or PA
Audible in Groups 2 (Part Set) and 3 (Night Set).
The programming of a zone in Group 1 (Full Set) also covers the unset condition.
9 — Fire
The Fire zone type is used for fire detection devices with normally closed outputs. No
means of smoke detector re-set is provided by the control panel.
It is strongly recommended that a zone programmed as Fire is programmed in one of
the following ways:
• Programmed as Fire in Groups 1 (Full Set), 2 (Part Set) and 3 (Night Set).
• Programmed as Fire in Group 1 (Full Set), and, 0 (Not Used) or Fire in Groups
2 (Part Set) and 3 (Night Set).
The programming of a zone in Group 1 (Full Set) also covers the unset condition.
Activation of a Fire zone at any time causes the Loud-Speaker, keypad sounder and
Bell outputs to pulse on and off.
21