Swimming Pool - Siemens AVS75.39 Series User Manual

Boiler controller
Table of Contents

Advertisement

Summary
Setpoints
Setpoint solar heating
Setpoint source heating
Priority
86 / 239
Siemens
Building Technologies
6.7

Swimming pool

B13
T
Q19
Line no.
Operating line
2055
Setpoint solar heating
2056
Setpoint source heating
When using solar energy, the swimming pool is heated up to this setpoint.
The "Protective collector overtemperature" function can reactivate the collector
pump until the maximum swimming pool temperature is reached.
Solar swimming pool heating can be dependent on a release via one or two Hx
inputs.
When using heating by the heat source, the swimming pool is heated up to this
setpoint.
Line no.
Operating line
2065
Charging priority solar
Priority 1 ¦ Priority 2 ¦ Priority 3
Priority 1
Swimming pool charge has the highest priority.
Priority 2
Swimming pool charge is second priority (after buffer storage tank and DHW
storage tank).
Priority 3
Swimming pool charge is without priority (after buffer storage tank, DHW storage
tank, heating circuits, consumer circuits).
Release and priority can also be influenced using Hx inputs.
User manual RVS43.345
The settings in detail
The controller facilitates swimming pool heating with
solar energy or heat generation based on separately
adjustable setpoints. In the case of solar heating, it is
possible to select priority of swimming pool heating over
storage tank charging.
CE1U2354en_021
2013-09-02