Siemens AVS75.39 Series User Manual page 87

Boiler controller
Table of Contents

Advertisement

Swimming pool temp
max
Plant hydraulics
Solar integration
Siemens
Building Technologies
Line no.
Operating line
2070
Swimming pool temp max
If the swimming pool temperature reaches the maximum limit set here, the collector
pump is deactivated. It is released again when the swimming pool temperature
drops 1 °C below the maximum temperature limit.
T
TSbMax
TSb
1
L
0
TSbMax
Swimming pool temperature max (2070)
TSb
actual value of the swimming pool temperature
L
Storage tank charging: 1 = on, 0 = off
Line no.
Operating line
2080
With solar integration
This setting is made to indicate whether the swimming pool can be charged by
solar energy.
User manual RVS43.345
The settings in detail
1°C
t
87 / 239
CE1U2354en_021
2013-09-02