Boiler controller
Table of Contents

Advertisement

Setpoints
Release
Example
Example
80 / 239
Siemens
Building Technologies
Line no.
Operating line
1610
Nominal setpoint
1612
Reduced setpoint
1614
Nominal setpoint max
The DHW can be heated up according to different setpoints. These setpoints are
activated depending on the selected operating mode, thus leading to different
temperature levels in the DHW storage tank.
TWWR
0
10
20
30
DHWR
Reduced DHW setpoint
TWWN
Nominal DHW setpoint
TWWmax
Nominal DHW setpoint maximum
Line no.
Operating line
1620
Release
24h/day ¦ Time programs HCs ¦ T'prog 4/DHW or low-tariff
24h / day
The DHW temperature is constantly maintained at the nominal DHW setpoint,
independent of any time programs.
0
6
Time programs HCs
The DHW setpoint changes between the nominal DHW setpoint and the reduced
DHW setpoint according to the heating circuits' time program. The first switch-on
point of each phase is shifted forward in time by 1 hour.
0
5
6
User manual RVS43.345
The settings in detail
TWWN
TWWmax
40
50
60
70
80
12
18
12
16 17
90
100
°C
h
24
h
24
CE1U2354en_021