Siemens AVS75.39 Series User Manual page 166

Boiler controller
Table of Contents

Advertisement

Operating action H1, H3
Input/function value H1,
H3
Input value 1
Function value 1
Input value 2
Function value 2
Example for consumer
circuit request CC1 10V.
166 / 239
Siemens
Building Technologies
Temperature measurement 10V (Analog input)
The controller receives the measured temperature signal as a voltage signal (DC
0...10 V).
The respective temperature is calculated via the linear characteristic which is
defined by 2 fixed points (input value 1 / input value 1 and input value 2 / function
value 2).
Use of measured temperature is defined via the parameter "Temperature sensor
H1, H3" (line 5957, 5967).
Setting unavailable with H2.
Line no.
5951, 5961
Break contact (NC)
The contact is normally closed and must be opened to activate the selected
function.
Make contact (NO)
The contact is normally open and must be closed to activate the selected function.
Line no.
5953, 5963
5954, 5964
5955, 5965
5956, 5966
These settings are available for each input Hx.
The linear characteristic is defined via 2 fixed points. The setting occurs using two
parameter pairs for input value and voltage value (F
The setting "Flow measurement Hz" converts the voltage value to a frequency
value.
TVLw [°C]
F
=130
2
F
=0
1
U
=0V
0.15 V
1
TVLw Flow temperature setpoint
Hx
Input value at Hx
U1
Input value 1
F1
Function value 1
U2
Input value 2
F2
Function value 2
If the input signal drops below the limit value of 0.15 V, the heat request is invalid
and therefore inactive.
User manual RVS43.345
The settings in detail
Operating line
Contact type H1, H3
NC ¦ NO
Operating line
Input value 1 H1, H3
Function value 1 H1, H3
Input value 2 H1, H3
Function value 2 H1, H3
U
=10V
2
/U
and F
/U
).
1
1
2
2
Hx [V]
CE1U2354en_021
2013-09-02