Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range
from –50 to +50°C can be simulated. During simulation, the current, mixed, and
attenuated outside temperature is overridden using the set simulation temperature.
During simulation, calculation of the 3 mentioned outside temperatures continues
and the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically
after a timeout of 1 hour.
Line no.
Operating line
7170
Telephone customer service
Setting of phone number that appears on the info display.