Siemens AVS75.39 Series User Manual page 136

Boiler controller
Table of Contents

Advertisement

Overtemperature
protection
Storage tank temp max
Recooling
Recooling temp
Recooling heat gen/HCs/
consumer circuit
Recooling collector
136 / 239
Siemens
Building Technologies
Line no.
Operating line
5050
Charging temp max
5051
Storage tank temp max
The DHW storage tank is charged by solar energy to the set maximum DHW
charging value.
Function "Overtemperature protection for the collector" can reactivate the collector
pump until the maximum storage tank temperature is reached.
If the storage tank reaches the maximum storage tank temperature set here,
charging is aborted. It will be released again when the storage tank temperature
has dropped 1 °C below the maximum.
T
TSpMax
TSp
1
L
0
TSpMax
Storage tank temp max (operating line 5051)
TSp
Storage tank temperature actual value
L
Storage tank charging: 1 = on, 0 = off
Line no.
Operating line
5055
Recooling temp
5056
Recooling heat gen/HCs
Off ¦ On
5057
Recooling collector
Off ¦ Summer ¦ Always
An activated "Recooling" function remains active until the set recooling temperature
in the DHW storage tank is reached.
Surplus energy can be drawn off either by the heating circuits/consumer circuits or
the generator. This can be selected separately for each heating circuit / consumer
circuit (operating page "Heating circuit / consumer circuit X...")
When the collector is cold, the excess energy can be emitted to the environment
via the collector's surfaces.
User manual RVS43.345
The settings in detail
1°C
t
CE1U2354en_021
2013-09-02