Siemens AVS75.39 Series User Manual page 71

Boiler controller
Table of Contents

Advertisement

Release
24 hours a day
Time programs, HCs
Time program 5 / DHW
Cooling curve
Flow temperature
setpoint
Flow setp at
OT 25°C
Flow setp at
OT 35°C
Siemens
Building Technologies
Line no.
Operating line
907
Release
24h/day ¦ Time programs HCs ¦ Time program 5
Parameter "Release" determines the time program in accordance with which
cooling is enabled.
Cooling is permanently enabled (24 hours a day)
Cooling is enabled in accordance with the heating circuit's time program
Release of cooling takes place in accordance with time program 5.
Line no.
Operating line
908
Flow temp setp at OT 25°C
909
Flow temp setp at OT 35°C
Based on the cooling curve, the controller determines the required flow
temperature at a certain composite outside temperature. The cooling curve is
determined by defining 2 fixed points (flow temperature setpoint at 25 °C and
35 °C).
This determines the flow temperature required for cooling at a composite outside
temperature of 25°C without giving consideration to summer compensation.
Determines the flow temperature required for cooling at a composite outside
temperature of 35°C , without giving consideration to summer compensation.
TVKw
908
909
25°C
TVKw
Flow temperature setpoint for cooling
TAgem
The composite outside temperature
The set cooling curve is based on a room temperature setpoint of 25°C . If the
room temperature setpoint is changed, the cooling curve is automatically adapted.
User manual RVS43.345
The settings in detail
35°C
TAgem
CE1U2354en_021
71 / 239
2013-09-02