Storage tank setpoints
Charging time relative
prio
Waiting time relative prio
Waiting time parallel op
Delay secondary pump
"Start" function
Collector start function
Min run time collector
pump
Siemens
Building Technologies
Level
DHW storage tank
A
Line 1610
B
Line 5050
C
Line 5051
* When priority for the swimming pool is activated ("Charging priority solar", line 2065), the swimming
pool is heated before the storage tanks are charged
1610: Nominal setpoint
5050: Charging temp max
5051: Storage tank temp max
4750: Charging temp max
4751: Storage tank temp max
2055: Setpoint solar heating
2070: Swimming pool temp max
If the preferred storage tank cannot be charged in accordance with charging
control, priority is transferred to the next storage tank or the swimming pool for the
period of time set (e.g. temperature differential between collector and storage tank
too great).
As soon as the preferred storage tank (according to setting "Charging prio storage
tank") is again ready to be charged, the transfer of priority will immediately be
stopped.
If the parameter is deactivated (---), priority always follows the settings "Charging
priority storage tank".
During the period of time set, the transfer of priority is delayed. This prevents
relative priority from intervening too often.
If solar output is sufficient and solar charging pumps are used, parallel operation is
possible. In that case, the storage tank of the priority model can be the next to be
charged at the same time, in addition to the storage tank to be charged next.
Parallel operation can be delayed by introducing a waiting time. This way, in the
case of simultaneous operation, switching on of the storage tanks can be effected
in steps.
Setting (---) disables parallel operation.
To remove any existing cold water from the primary circuit, operation of the
secondary pump of the external heat exchanger can be delayed.
Line no.
Operating line
3830
Collector start function
3831
Min run time collector pump
3832
Collector start function on
3833
Collector start function off
3834
Collector start funct grad
3835
Min collector temp start fct
If the temperature at the collector (especially in the case of vacuum tubes) cannot
be correctly acquired when the pump is deactivated, the pump can be activated
from time to time. This setting defines the interval at which the collector pump is put
into operation. Then, the pump will operate for the set time "Min run time collector
pump" (3831).
The collector pump remains switched on at a minimum for the parameterized
minimum running time.
User manual RVS43.345
The settings in detail
Buffer storage tank
Buffer setpoint (slave pointer)
Line 4750
Line 4751
Swimming pool*
Line 2055
Line 2055
Line 2070
115 / 239