Siemens AVS75.39 Series User Manual page 150

Boiler controller
Table of Contents

Advertisement

Heating circuit 2
Heating circuit 2
Heating circuit 3
Heating circuit 3
DHW sensor B3
150 / 239
Siemens
Building Technologies
Line no.
Operating line
5715
Heating circuit 2
Off ¦ On
Using this setting, heating circuit 2 can be switched on and off.
Line no.
Operating line
5721
Heating circuit 3
Off ¦ On
Using this setting, heating circuit 3 can be switched on and off.
Line no.
Operating line
5730
DHW sensor B3
Sensor ¦ Thermostat
Sensor
The collector calculates the switching points including the switching differential
from the DHW setpoint and the acquired DHW storage tank temperature.
Thermostat
The DHW temperature is controlled based on the switching state of a thermostat
connected to B3.
When using a DHW control thermostat, Reduced mode is not possible. This means
that when Reduced mode is active, DHW heating with the thermostat is locked.
The adjustment of the nominal DHW temperature setpoint must be equal to or
higher than the setpoint adjustment on the thermostat (thermostat calibrated at
switch-off point)
The flow temperature setpoint for DHW must be set to a minimum of 10 °C (with
impact on the charging time)
DHW frost protection is not guaranteed.
User manual RVS43.345
The settings in detail
CE1U2354en_021
2013-09-02