Individual Feed

An individual feed shelf is fed by four (4) AC feeds; each feed supplies one
rectifier and should have 15A breakers. The figure below illustrates the 9-pin AC
input connector. Termination points for Line 1,
Line 2, and Ground are listed in the table at right.
#12 AWG wire is recommended for each 15A
circuit, but up to #10 AWG may be used for each
feed termination position.
1
Figure 4 - Individual Feed Connector (Cover Removed)

Dual Feed

A dual feed shelf is fed by two (2) AC feeds; each feed supplies two rectifiers and
should have 30A breakers.
connector. Termination points for Line 1, Line 2, and Ground are listed in the
table at right. #10 AWG wire is recommended for
each 30A circuit.
Installation Guide Flatpack2 -48V 150A ~ 2029242 R2, May 2008
Ground Termination
9
The figure below illustrates the 5-pin AC input
Ground Termination
1
5
Figure 5 - Dual Feed Connector (Cover Removed)
Pin Description
Line 1, Rectifier 1
1
Line 2, Rectifier 1
2
Line 1, Rectifier 2
3
Line 2, Rectifier 2
4
Line 1, Rectifier 3
5
Line 2, Rectifier 3
6
Line 1, Rectifier 4
7
Line 2, Rectifier 4
8
Ground
9
Pin Description
Line 2, Rectifier 1 & 2
1
Line 2, Rectifier 3 & 4
2
Line 1, Rectifier 1 & 2
3
Line 1, Rectifier 3 & 4
4
Ground
5
11

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Flatpack2 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF