System overview
2.3 Technical specifications
2.3
Technical specifications
Technical data
Unless specified otherwise, the following technical specifications are valid for all the following
components of the water-cooled SINAMICS S120 drive system.
Table 2- 1
General technical data
Electrical data
Line supply voltage
Line frequency
Output voltage
Output frequency
Electronics power supply
Short-circuit current rating per IEC, in
conjunction with the specified fuses or
circuit breakers
Rated short-circuit current SCCR (Short
Circuit Current Rating) in accordance with
UL508C (up to 600V), in conjunction with
the specified fuses or circuit-breakers
Frequency with which the DC link is pre-
charged
Interference suppression
Overvoltage category
Mechanical data
Vibratory load
Transport
•
2)
Operation
•
Shock load
Transport
•
2)
Operation
•
30
3 AC 380 V -10% (-15% < 1 min) ... 3 AC 480 V +10%
•
3 AC 500 V -10% (-15% < 1 min) ... 3 AC 690 V +10%
•
47 ... 63 Hz
0 to line connection voltage, depending on the type of infeed.
With an Active Line Module, it is also possible to achieve a higher output volt-
age.
Vector control: 0 ... 550 Hz
Servo control: 0 ... 550 Hz
V/f control: 0 ... 550 Hz
1)
24 V DC (20.4V ... 28.8V)
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = Negative polarity grounded via the electronics
1.1 ... 447 kW: 65 kA
•
448 ... 671 kW: 84 kA
•
672 ... 1193 kW: 170 kA
•
>1194 kW: 200 kA
•
1.1 ... 447 kW: 65 kA
•
448 ... 671 kW: 84 kA
•
672 ... 1193 kW: 170 kA
•
>1194 kW: 200 kA
•
Max. 1 precharge every 3 minutes
Category C3 (second environment) according to EN 61800-3
Class III according to EN 61800-5-1
EN 60721-3-2, class 2M2
•
Test values according to EN 60068-2-6 test Fc:
•
–
10 ... 58 Hz with constant deflection = 0.075 mm
–
58 Hz with constant acceleration = 9.81 m/s² (1g)
EN 60721-3-2, class 2M2
•
Test values according to EN 60068-2-27 test Ea: 98 m/s² (10g) / 20ms
•
Water-cooled chassis power units for common cooling circuits
1)
1)
Manual, 08/2017, 6SL3097-4AM10-0BP0