Technical specifications

Converters for Canadian installations (cUL): FSA ... FSC
In order that the system is cUL-compliant, use cUL-certified fuses type J or Siemens fuses of
the 3NE1 type. Use only copper wire approved for 75°C .
Install the converter with any external recommended suppressor with the following features:
● Surge-protective devices; device shall be a listed surge-protective device (Category code
● Rated voltage 3-ph. 480/277 VAC, 50/60 Hz
● Clamping voltage V
● Suitable for type 1 or type 2 SPD application
● Clamping shall be provided between the phases and also between phase and ground
Alternatively use the surge-protective device from Siemens AG, order no. 5SD7 424-1, to
fulfil the cUL requirements
Converters for installation in the U.S. (UL): FSA ... FSF
In order that the system is UL-compliant, use the fuses listed in section Specifications
(Page 44). Use only copper wire approved for 75°C .
Power Module PM230, IP20 / Push through
Hardware Installation Manual, 03/2012, A5E03448282B AA
VZCA7)
PR
= 2000 V, I
= 3 kA min, MCOV = 550 VAC, SCCR = 65 kA
N
6
41