X42 Terminal Strip; X46 Brake Control And Monitoring - Siemens SINAMICS S120 Equipment Manual

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.3.6

X42 terminal strip

Table 6- 5
Max. connectable cross-section: 2.5 mm
Note
Connection options of terminal strip X42
The terminal strip is not intended to generally provide a 24 V DC supply (for example for
supplying additional components on the plant or system side), as the voltage supply of the
Control Interface Module could also be overloaded and the correct functioning could thus be
compromised.
6.3.7

X46 Brake control and monitoring

Table 6- 6
Max. connectable cross-section: 1.5 mm
Note
The interface is intended for connection of the Safe Brake Adapter.
Fire hazard due to overheating when permissible connection cable lengths are exceeded
Excessively long connection cables on terminal strip X46 can cause components to
overheat with the associated risk of fire and smoke.
• Limit the length of the connecting cables to a maximum of 10 m.
• The connection cable must not be led out the control cabinet or control cabinet group.
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
Function
1
P24L
2
3
M
4
Terminal strip X46 brake control and monitoring
Terminal
Function
1
BR output +
2
BR output -
3
FB input +
4
FB input -
WARNING
Technical data
Power supply for Control Unit, Sensor Module
and Terminal Module (18 ... 28.8 V)
maximum load current: 3 A
2
Technical data
Brake connection
Supply voltage: 24 V DC
Max. load current: 0.2 mA
2
Motor Modules
6.3 Interface description
147