All components in the cooling system (SINAMICS units, heat exchanger, piping system,
pump, pressure compensator, etc.) must be connected to an equipotential bonding system.
This must be realized using a copper bar or stranded copper with the appropriate conductor
cross-sections to prevent electrochemical processes from occurring.
If the installation comprises more than one control cabinet, they must be bolted together to
establish a good electrical connection (e.g. bolt cabinet cross-beams together directly at
several points to establish a good electrical connection). This eliminates potential differences
and thus the risk of electrochemical corrosion. A PE bar must be installed in every cabinet
(including the recooling system) and the individual bars then interconnected.