Emerson Rosemount 3051CF Series Quick Start Manual page 39

Pressure transmitter and flow meter
Hide thumbs Also See for Rosemount 3051CF Series:
Table of Contents

Advertisement

October 2019
Table 9-8: Input Parameters (continued)
Parameter
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is not capable of withstanding the 500 V insulation test required by
ABNT NBR IRC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if equipment requires EPL Ga.
9.6.3
IB INMETRO FISCO
Certificate UL-BR 13.0584X
Standards ABNT NBR IEC60079-0:2013, ABNT NBR IEC60079-11:2013
Markings
Table 9-9: Input Parameters
Parameter
Voltage U
Current I
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient suppressor,
it is not capable of withstanding the 500 V insulation test required by
ABNT NBR IEC 60079-11. This must be taken into account when
installing the equipment.
2. The enclosure may be made of aluminum alloy and given protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if equipment requires EPL Ga.
Quick Start Guide
HART
0 mH
i
Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ +60 °C)
i
i
i
i
Fieldbus/PROFIBUS
0 mH
FISCO
17.5 V
380 mA
5.32 W
≤5 nF
≤10 µH
Quick Start Guide
39