Emerson Rosemount 3051CF Series Quick Start Manual page 30

Pressure transmitter and flow meter
Hide thumbs Also See for Rosemount 3051CF Series:
Table of Contents

Advertisement

Quick Start Guide
9.3.2
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Range 1-5
(HART)
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is
considered a potential risk of ignition by impact or friction. Care must
be taken into account during installation and use to prevent impact
and friction.
2. The Model 3051 transmitter with the transient terminal block
(Option code T1) will not pass the 500 Vrms dielectric strength test,
and this must be taken into account during installation.
Range 1-6
(HART/
Fieldbus/
PROFIBUS)
Certificate
Standards
Markings
9.3.3
IE USA FISCO
Range 1-5
(HART)
Certificate
30
FM16US0120X
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class
3611 - 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III;
DIV 1 when connected per Rosemount drawing
03031-1019; NI CL 1, DIV 2, GP A, B, C, D; T4 (–50 °C ≤ T
+70 °C) [HART], T4 (–50 °C ≤ T
PROFIBUS]; Type 4X
1053834
ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987,
CSA Std. C22.2. No.157-92
IS Class I, II, III, Division 1 Groups A, B, C, D, E, F, and G
when connected in accordance with Rosemount drawing
03031-1024, Suitable for Class I, Zone 0 Group IIC; Class I,
Division 2, Groups A, B, C, and D; NIFW; Suitable for Class
I, Zone 2, Group IIC;
HART: T4 (–60 °C ≤ Ta ≤ +70 °C), T5 (–60 °C ≤ Ta ≤ +40 °C)
Fieldbus/PROFIBUS: T4 (–60 °C ≤ Ta ≤ +60 °C)
Type 4X
FM16US0120X
October 2019
≤ +60 °C) [Fieldbus/
a
Rosemount 3051
a