on painted surfaces and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
9.4.2
I1 ATEX Intrinsic Safety and Dust
Certificate BAS97ATEX1089X; Baseefa11ATEX0275X
Standards EN60079-0:2012 + A11:2013, EN60079-11:2012,
Markings
Table 9-2: Input Parameters
Parameter
Voltage U
Current I
Power P
i
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation
test required by clause 6.3.12 of EN60079-11: 2012. This must be
taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion of located in Zone 0.
3. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
9.4.3
IA ATEX FISCO
Certificate
Standards
Quick Start Guide
EN60079-31:2014
HART:
II 1 G Ex ia IIC T5/T4 Ga, T5 (-60 °C ≤ Ta ≤ +40 °C), T4
(-60 °C ≤ Ta ≤ +70 °C)
Fieldbus/PROFIBUS:
°C)
DUST:
II 1 D Ex ta IIIC T95 °C T
+85 °C)
HART
30 V
i
200 mA
i
0.9 W
0.012 µF
i
0 mH
i
BAS97ATEX1089X
EN60079-0:2012 + A11:2013, EN60079-11:2012
II 1 G Ex ia IIC Ga T4 (-60 °C ≤ Ta ≤ +60
105 °C Da (-20 °C ≤ Ta ≤
500
Fieldbus/PROFIBUS
30 V
300 mA
1.3 W
0 µF
0 mH