Advertisement

October 2019
Standards IEC60079-0:2011, IEC60079-1:2014-06,
Markings
Table 9-4: Process Temperature
Temperature class
T6
T5
T4
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thick that
forms a boundary between EPL Ga (process connection) and EPL Gb
(all other parts of the equipment). The model code and datasheet are
to be consulted for details of the diaphragm material. During
installation, maintenance, and use, the environmental conditions to
which the diaphragm will be subjected shall be taken into account.
The manufacturer's instructions for installation and maintenance
shall be followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Some variants of the equipment have reduced markings on the
nameplate. Refer to the Certificate for full equipment marking.
9.5.2
I7 IECEx Intrinsic Safety
Certificate IECEx BAS 09.0076X
Standards IEC60079-0:2011, IEC60079-11:2011
Markings
Quick Start Guide
IEC60079-26:2014-10, IEC60079-31:2013
Ex db IIC T6...T4 Ga/Gb T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C
≤ Ta ≤ +80 °C); Ex ta IIIC T95 °C T
+85 °C)
Process connection temperature
–60 °C to +70 °C
–60 °C to +80 °C
–60 °C to +80 °C
HART: Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ Ta ≤ +40 °C), T4 (-60 °C ≤
Ta ≤ +70 °C)
Fieldbus/PROFIBUS: Ex ia IIC T4(–60 °C ≤ Ta ≤ +60 °C)
Quick Start Guide
105 °C Da (-20 °C ≤ Ta ≤
500
35