Changing Battery Capacity Rating in the NCU
NOTE!
After setting the battery capacity, the User should also reset the battery capacity (battery must
be fully charged).
1.
Change the battery capacity setting of the NCU to match the total capacity of all battery strings
connected to the power system.
Local Menu Navigation:
Main Menu / Settings Icon / Batt Settings / Batt1 Settings / Rated Capacity.
Web Menu Navigation:
Settings Menu / Battery Tab / Batt1 Rated Capacity.
2.
Reset the battery capacity (resets the battery capacity calculation).
NOTE!
Only reset the battery capacity when the battery is fully charged; otherwise, the battery charge
status may not be accurate.
Local Menu Navigation:
Main Menu / Settings Icon / Batt Settings / Basic Settings / Reset Batt Cap.
Web Menu Navigation:
Settings Menu / Battery Tab / Reset Battery Capacity.
Refer to the NCU Instructions (UM1M830BNA) for detailed instructions.
Configuring the NCU Identification of Rectifiers and
Assigning which Input Feed is Connected to the Rectifiers (Optional)
When rectifiers are all installed prior to applying power and starting the system, the order in which the NCU
identifies the rectifiers is by serial number (lowest serial number is Rect 1, next lowest is Rect 2, etc.). If you
prefer the NCU to identify the rectifiers by position in the system, perform the following procedure.
Upon power up, the NCU arbitrarily assigns Feed AC1, AC2, or AC3 to each rectifier. This assignment is used to
display rectifier AC input feed voltage(s). The User may reassign the feed to each rectifier per your specific
installation by following the procedure below.
Local Menu Navigation:
None.
Web Menu Navigation:
Refer to the NCU Instructions (UM1M830BNA) for detailed instructions.
Configuring the NCU Identification of Converters (Optional)
When converters are all installed prior to applying power and starting the system, the order in which the NCU
identifies the converters is by serial number (lowest serial number is Conv 1, next lowest is Conv 2, etc.). If you
prefer the NCU to identify the converters by position in the system, perform the following procedure.
Local Menu Navigation:
None.
Vertiv
| NetSure 7100 Series Installation Manual (IM582127000100) | Rev. H