Vertiv NetSure 7100 Series Installation Manual page 59

48v dc power system
Hide thumbs Also See for NetSure 7100 Series:
Table of Contents

Advertisement

NOTE!
Three battery temperature probes are provided. Connect a temperature probe to the left-most
battery module's negative terminal in each battery tray (see
in the bottom tray to the System Temp 1 input on the system interface board. Connect the temperature
probe in the middle tray to the System Temp 2 input on the system interface board. Connect the
temperature probe in the top tray to the Temp 1 input on the IB2-1 board. Refer to "Temperature
Probes" on page 37. In the event there is excess length of the probe wires, coil the wires up and tie in a
convenient location along the path of the battery power cable. For systems equipped with fewer than
three battery strings in the power bay, the unused temperature probes should be programmed off. Refer
to the controller user manual, UM1M830BNA, provided with the system for instructions.
8.
Repeat steps 1 through 7 for any remaining battery trays.
9.
To connect the batteries to the power system, turn ON the battery disconnect circuit breaker located on
all battery trays.
Vertiv
| NetSure 7100 Series Installation Manual (IM582127000100) | Rev. H
Figure 28
). Connect the temperature probe
59

Advertisement

Table of Contents
loading

Table of Contents