the User. Note that only Users programmed into the NCU are shown. Users are programmed via the
Web Interface. The default User is admin.
3.
To Enter a Password:
To enter a password, use the UP and DOWN keys to move the cursor to the Enter Password field. Press
ENT. Use the UP and DOWN keys to choose a character. Press ENT to accept and move to the next
character. Continue this process until all characters are entered. Press ENT again to accept the
password. The default password is 640275.
4.
To Change a Parameter:
Press the UP and DOWN keys to move up and down the list of parameters. Press ENT to select the
parameter. Press the UP and DOWN keys to change the parameter. Press ENT to make the change.
Press ESC to cancel the change.
Table 11 shows the menu navigation for some basic settings. Refer to the separate NCU Manual
(UM1M830BNA) supplied with your power system for complete Local Display menus.
Table 11:
NCU Basic Settings Menu Navigation
Parameter
Date
Time
IP Communications
Parameters
(IP address, subnet mask
address, gateway address)
Float Voltage
Equalize Voltage
Battery Capacity
Reset Battery Capacity
Battery Charge Temperature
Compensation
Rectifier Current Limit
Over Voltage Alarm 1
Over Voltage Alarm 2
Under Voltage Alarm 1
Under Voltage Alarm 2
NOTE!
All above parameters are preset at the factory and should not need to be adjusted with the
exception of the date, time, and battery capacity.
Vertiv
| NetSure 7100 Series Installation Manual (IM582127000100) | Rev. H
Menu Navigation
Main Menu / Settings Icon / Sys Settings / Date.
Main Menu / Settings Icon / Sys Settings / Time.
Main Menu / Settings Icon / Comm Settings / enter parameters.
Main Menu / Settings Icon / Batt Settings / Charge / Float Voltage.
Main Menu / Settings Icon / Batt Settings / Charge / EQ Voltage.
Main Menu / Settings Icon / Batt Settings / Batt1 Settings / Rated
Capacity.
Main Menu / Settings Icon / Batt Settings / Basic Settings / Reset Batt
Cap
Main Menu / Settings Icon / Batt Settings / Temp Comp (enter
parameters).
Main Menu / Settings Icon / Rect Settings / Current Limit (set to
enabled) then set Curr Limit Pt.
Main Menu / Settings Icon / Other Settings / Over Voltage 1.
Main Menu / Settings Icon / Other Settings / Over Voltage 2.
Main Menu / Settings Icon / Other Settings / Under Voltage 1.
Main Menu / Settings Icon / Other Settings / Under Voltage 2.
69