Block In-Use: Set to number of 12V battery blocks being used.
Programmable Relay Outputs
The optional EIB provides five (5) programmable alarm relays with dry Form-C contacts. Connect up to five (5)
relay outputs to the EIB. Refer to Figure 21 for terminal locations and Table 9 for pin-out information.
Refer to the NCU Instructions (UM1M830BNA) for programming information.
Relay Ratings: Refer to the following.
a)
Steady State: 0.5 A @ 60V DC; 1.0 A @ 30V DC.
b)
Peak: 3 A @ 30V DC.
The relays may be preprogrammed for specific functions. Refer to the configuration drawing (C-drawing)
supplied with your system for your system's specific configuration.
Temperature Probes
Two temperature probes can be connected to the optional EIB (Controller Extended Interface Board) mounted
inside the distribution cabinet. Refer to "Temperature Probes" on page 37.
Vertiv
| NetSure 7100 Series Installation Manual (IM582127000100) | Rev. H