Siemens MK8000 MP4.30 Installation/Configuration Manual page 89

Opc server for subsystems
Hide thumbs Also See for MK8000 MP4.30:
Table of Contents

Advertisement

Building Technologies
Fire Safety & Security Products
Fig. 89
Getting detailed status information
Starting the MK8000 Server in Simulation mode
In the Advanced menu, you can start the MK8000 server in simulation mode. This
mode results in starting an additional application (Field Simulator), which allows
generating messages as though they were coming from the fire and intrusion con-
trol units in the field.
The Field Simulator (Fig. 90) presents a user interface quite similar to the Testing
Client application (e.g. see Fig. 70).
A tree structure on the left pane (Fig. 90-A) allows for selecting the field objects.
When an object is selected, the corresponding properties are listed in the top right
pane (Fig. 90-B). In this list, clicking the 'Value' field and picking up one the condi-
tions allows for modifying the property state, thus simulating a field message gen-
erated by the control unit.
The pane at the bottom right (Fig. 90-C) presents the simulation logging, where all
messages are registered.
Fig. 90
Field Simulator
A
Object tree
Hierarchical tree including control units and objects configured in MK8000
Tips for Integrating with an OPC client
048_DMS_MK8000_ICC_MP4.30_A6V10062407_a_en
89
06.2010

Advertisement

Table of Contents
loading

Table of Contents