Siemens Synco OZW772 Series Commissioning Instructions

Siemens Synco OZW772 Series Commissioning Instructions

Web server v6.0 for synco system
Hide thumbs Also See for Synco OZW772 Series:
Table of Contents

Advertisement

s
Synco™, Synco™ living
Web server OZW772... V6.0
Commissioning instructions
CE1C5701en
2015-10-12
OZW772.01
OZW772.04
OZW772.16
OZW772.250
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Synco OZW772 Series

  • Page 1 OZW772.01 Synco™, Synco™ living OZW772.04 Web server OZW772... V6.0 OZW772.16 OZW772.250 Commissioning instructions CE1C5701en Building Technologies 2015-10-12...
  • Page 2 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 © Siemens Switzerland Ltd, 2009 www.siemens.com/buildingtechnologies Subject to change 2 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies 2015-10-12...
  • Page 3: Table Of Contents

    Remote access via portal ..............44 Set up access via portal ............... 44 3.1.1 Portal and plant roles ................48 Prevent connection to portal ..............48 3 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Table of contents 2015-10-12...
  • Page 4 Dialog boxes with enumeration data points .......... 97 7.4.4 Dialog boxes with variable unit data points ........... 98 7.4.5 Dialog boxes for data points with manually set value ......99 4 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Table of contents 2015-10-12...
  • Page 5 Free e-mail account providers ............161 11.3.3 Install RNDIS driver ................162 11.3.4 Alternative network configuration ............164 11.4 Glossary of Ethernet and Internet terms ..........165 Index ......................172 5 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Table of contents 2015-10-12...
  • Page 6 6 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Table of contents 2015-10-12...
  • Page 7: Overview

    · Do not open the device. Failure to comply will invalidate any warranty claims. · The technical data are provided solely for use with Siemens bus devices. The user ensures the functionality of operation when using third-party devices not expressly mentioned here.
  • Page 8 Directive 2012/19/EU and may not be disposed of as domestic waste. · Dispose of the device via the proper channels. · Comply with all local and currently applicable laws and regulations. 8 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 9: Web Server Display And Operating Elements

    History data is not deleted. Switches · Position ON Message Sending messages is suppressed · Position OFF suppression Sending messages permitted · Switch settings No function DIP switch 2 9 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Overview 2015-10-12...
  • Page 10: User Interface

    · Orange leaf: One or multiple "Energy indicator" data points are outside their "green limits" Clicking the "Plant state Energy indicator" field opens the "Energy indicator" function. 10 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Overview 2015-10-12...
  • Page 11: User Levels

    · Documents, message history Administrator Same as service. In addition: · Create device list and web pages · The toolbar to create plant web pages · Administer all user accounts 11 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Overview 2015-10-12...
  • Page 12: Symbols, Notations, Abbreviations

    System definitions Logos Switch over displays: Full view, partial view Fault indication: Green field = no fault; red field = fault (alarm) "Green leaf" "Orange leaf" "Grey leaf" 12 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Overview 2015-10-12...
  • Page 13: Notations

    OZW772.01 or OZW772.04 or OZW772.16 or OZW772.250 IP address, domains Enter in the browser address line: · IP address: 192.168.2.10 · Domain: www.siemens.com · Portal: https://www.siemens-syncoic.com Buttons Buttons depicted as follows: [ Add ] 1.4.3 Abbreviations Abbreviations Auto MDI-X Auto Medium Dependent Interface – Crossed.
  • Page 14: Commissioning

    · To navigate, always start with primary navigation, then use the secondary Operating notes navigation to select the desired menu item. · Return: Click "Upward" or navigate via the path or primary navigation. 14 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 15: Getting Started

    Internet and no RNDIS driver is installed as long as the Microsoft online update is enabled. Follow the instructions for the installation program. Note You can also manually setup the RNDIS driver (see Section 11.3.3). 15 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 16: Log Into Web Server

    · You cannot exit the dialog box if you do not define a new password (i.e. not equal to "Password or Password.1") and the following note is displayed: · The following message is displayed if you fail to fill out all required fields: 16 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 17 Minimum password length of 8 characters · At least 1 capital letter · At least 1 lowercase letter · At least 1 number · At least 1 special character · 17 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 18: Administer User Accounts

    Enter / Select user data: - User name - Password - Repeat password - Description (optional) - E-mail address (optional) - Language: English - User group Close with [ OK ] 18 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 19 · A secure password is comprised of letters, numbers and special characters, is at least 20 characters in length and does not include a name or words from dictionaries. 19 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 20: Create Device Web

    The serial number is located on the type label for Synco devices. Confirm with [ OK ] The Web Server searches for the device with the corresponding serial number. It appears in the device list if found. 20 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 21 The Web Server removes the device from the device list. Wait until the message " Process finished" is displayed. Click [ OK ] to confirm. The device is deleted from the device list. 21 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 22 When deleting or adding a Synco device (see above for description of workflow), we recommending copying (select and right-click: Copy) the serial number to the clipboard prior to deleting. 22 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 23: Web Server Settings

    The setting values are derived from the current time clock and the current date. Weekday is Default val: 00:00 1.1.2005 Setting val: Time of day/date calculated automatically. 23 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 24: Operating Page "Faults Current

    The time zone setting value is based on UTC — (GMT). The time zone also defines daylight Default val: GMT +01:00 Berlin, Rome saving time / standard time changeover. Setting val: misc. Time zones 24 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 25: Communication

    The following data points are information parameters. They are described in Section 4.2.3, "Web Server diagnostics": · Maximum number of devices · Current number of devices · Last change 25 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 26 Internet connects a globally valid name to a Default val: 192.168.2.1 Setting val: IP address domain with an IP address (e.g. domain www.siemens.com with IP address 146.254.191.150). The setting corresponds to the IP address for the next router or DNS server that recognizes for its part a queried name (domain) or another DNS server.
  • Page 27 Web Server registers its existence in the USB network, when · "UPnP localization = USB" is set and · The connection between PC/laptop and the Web Server is active via USB. 27 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 28: Message Receivers

    Web access via http Permits communication using the http protocol — rather than the secured https connection. Default value: Off Siemens recommends https. The user is Setting values: On/Off responsible for using http. UPnP localization The Web-Server registers its existence in the —...
  • Page 29 Web Server can send messages. Special day, The default value sends messages 00:00 On … throughout the entire period. Setting val: Monday - Sunday, Special day 00:00 - 24:00 Off/on 29 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 30 Event. Data and time can be used to indicated beginning Reason Annually and end of period. Select "Annually" to repeat the periods each year. 30 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 31: System Report

    "Urgent only" messages. Next report Waiting period until the next system report is — sent. Default val: 0 d (day) Setting val: 0...255 d 31 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 32: Consumption Data

    Web Server. Enable send of centralized due day. Send due day date — Default val: Off Setting val: Off, On 32 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 33: Energy Indicator

    Visibility of the "Energy indicator" can be defined: Path: Home > 0.2.150 OZW772.xx > Settings > Energy indicator The descriptions are available in Section 7.2.5 "Energy indicator" visibility". 33 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 34: Trend

    Web Server device list. A fault to Synco devices is displayed with the Note "System" faults refer to faults to the KNX device received via the KNX bus. 34 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 35: 2.5.3.10 Texts

    The operating page "Device information" displays information on Web Server, LPB/BSB, Ethernet, and services. Path: Home > 0.2.150 OZW772.xx > > Device information Descriptions are available in Section 4.2.3 "Web Server diagnostics". 35 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 36: Commission Network Components

    No additional settings required on the router. The workflow for access via portal is described in Section 3.1 "Set up access via portal". 2.6.2 Access via a local area network (LAN) 36 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 37: Access Via Direct Connection

    Port 80 is disabled by default. Access via http (Port 80) is unsecure. The user is responsible for enabling port 80. Always selected an https connection (Port 443 is enabled by default). 37 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 38 · Dynamic DNS: The dynamic IP address for the connection must be published if no fixed public IP address is available. Settings depend on network type and application. The different variants are described in Section 8.1.3, "Access via direct connection". 38 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 39: Functional Check

    The first cause is displayed for multiple faults. See the following table. Message inhibition Shows the message suppression switch — setting (8) (see Section 1.2). Display values: Yes, No 39 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 40 The fault message is reset if: Reset fault messages · The next e-mail is error free. · A manually triggered "Test message receiver" is successful. · The message receiver is deactivated. 40 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 41: Additional Settings

    Path: Home > 0.2.150 OZW772.xx > Settings > Faults Note We recommend deleting the history after you have completed commissioning. The workflow is described in Section 2.5.3.9, "Faults". 41 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning...
  • Page 42: Final Steps

    – The Web Server sends a system report to the defined message receivers. – Fault LED displays (flashing) error in establishing communications. LED On must be steady green. Fault LED must be off. 42 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 43: Supply State

    The current, installed version of system definitions is displayed in device info. Firmware update Local operation on Web Server required to update firmware. Procedures are communicated for any firmware update accordingly. Logo update The logos can be customized. 43 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Commissioning 2015-10-12...
  • Page 44: Remote Access Via Portal

    Remote access via portal Siemens offers with the Synco IC Internet portal simple and secure access to web serves (available as of Web Server version 5.2). It permits remote servicing of the plant at any time and from any location.
  • Page 45 Query portal The portal can be queried via the following domains: https://www.siemens-syncoic.com Operating language The button in the upper right corner selects the portal operating language. Registration Registration is required the first time the portal is used. Enter an e-mail address and activation key to register.
  • Page 46 One user can activate multiple plants. The number is based on assigned roles. plants The workflow for activating an additional plant is the same as described under "Activate plant". 46 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Remote access via portal...
  • Page 47 Web Server without portal (local or via the Internet). Operation is the same as described in Section 4.2, "Operate the plant". 47 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Remote access via portal...
  • Page 48: Portal And Plant Roles

    USB prior to connecting the device to the Ethernet. The device logs on independently to the portal as soon as it has a connection to the Internet. 48 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 49: Operate Using A Web Browser

    (e.g. IE10+, FF18+) via USB interface, LAN/Ethernet or Internet (with or without portal). Connection To access the portal, enter the address https://www.siemens-syncoic.com. For access without portal, enter the IP address for the interface (USB, Ethernet) or the plant’s domain name in the browser’s address line.
  • Page 50 Example Original URL: http://192.168.250.1/main.app?SessionId=f9d53187-2868-4a6b-8b20- 9eca4e859a4d&section=popcard&id=637&idtype=4 Available as "Deep Link": http://192.168.250.1/main.app?user=Administrator&pwd=myPassword& section=popcard&id=637&idtype=4 The current, valid login information must be included for syntax "user=<user name>&pwd=<myPassword>". 50 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 51: Operate The Plant

    KNX pages defined with ETS are also displayed here. Setting data on various operating pages is described in Section 2.5, "Web Server settings". 51 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser...
  • Page 52 Note In partial view, navigation to other plant web pages must be implemented using user-defined links. You can return to the full view at any time for navigation. 52 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser...
  • Page 53: Web Server Diagnostics

    Actual number of devices monitored by Web current Server on the Synco bus. Last change Time of last change to device list. — Ethernet 53 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 54 Alternative settings are used for the following when the DHCP client is switched off: Setting for DHCP client · IP address · Subnetmask · Standard gateway · Preferred DNS server · Alternative DNS server 54 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 55 With "Off" there is no exchange of data. Automatic log off "Absolute timeout" automatically disconnects to the Web Server after 24 hours. 55 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 56: Faults

    Setting val: Yes / No. Setting value "Yes" is a temporary state, i.e. the setting value automatically goes to "No" after ca. 2 seconds. 56 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser...
  • Page 57 Device name, Fault information, Fault text, Area, Line, Device address, Device type Note Faults for Synco devices are listed in the documentation for the corresponding devices. 57 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 58: File Transfer

    Select "Message history" from secondary navigation. Click for the desired document. TXT for text or ASCII format and XLS for Excel format. The "File download" dialog box opens. 58 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser...
  • Page 59 '15:42:26 5003: Invalid time of day Message not OK OZW772.01 (0.2.150) '2009.06.24 '15:42:26 5023: M'rec 1 not reached '2009.06.24 '15:42:38 1: myservice@siemens.com Fault receiver Message not OK OZW772.01 (0.2.150) '2009.06.24 '15:42:26 5023: M'rec 1 not reached '2009.06.24 '15:42:43 1: myservice@siemens.com...
  • Page 60 · The original logos are restored when resetting the Web Server to default. · The area belonging to the logo is highlighted in color when the cursor moves within the display area above the logo line. 60 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 61 Note Make sure there is at least 60 MB free memory on the Web Server when uploading. If not, check the contents via File transfer > Documents. 61 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser...
  • Page 62: Operation With Acs790

    (the parameter set of the OZW772… contains the device list of the OZW772…, too) · Commissioning protocol. · Offline trend. For more details, see data sheet N5649. 62 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Operate using a web browser 2015-10-12...
  • Page 63: Visualize Plants

    Download plant diagram Web-capable plant diagrams can be downloaded from the HIT (HVAC Integrated Tool by Siemens) online platform for Synco 700 devices, RXB/RXL room control- lers and RDG/RDF/RDU room thermostats standard applications. Create own plant web You can freely design plant web pages.
  • Page 64: Example Of A Plant Web Page

    As of OZW version 5.0, data points are also available on devices integrated via KNX S-Mode for display on the plant diagram (Light, blinds, energy volume meters, etc.). See Section 10 "KNX S-Mode". 64 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 65: Plant Web

    (current available memory is available at "File transfer > Documents"). · A maximum of 100 elements may be added on a plant web page from one web page element type (e.g. a maximum of 100 data point elements). 65 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 66: Toolbar

    (e.g. web cams). User levels Only an administrator may generate and change visualization. User levels have the same rights for operation and monitoring. 66 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Visualize plants...
  • Page 67: Import Web-Capable Plant Diagrams

    · The device web page is generated, see Section 2.4. The Web Server menu tree and data point information for the device and the loaded standard application are now available. Download plant Workflow in HIT online platform (Siemens HVAC Integrated Tool): diagram from HIT Run www.siemens.com/hit. Select country.
  • Page 68 · The data point text "Data point not found" is displayed. · Three question marks "???" are displayed as the data point value. See Section 5.6 for any post editing. 68 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 69: Create Own Plant Web

    If satisfied, click OK to finish. 10. Click OK to change to view. The data point value was read and is displayed. 69 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Visualize plants 2015-10-12...
  • Page 70 The following describes how to add two lines to the plant web page: · To another plant web page. · To an external web page. The link to a document is not displayed, but works accordingly. 70 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Visualize plants...
  • Page 71 12. If satisfied, click OK to finish. 13. Click OK to change to view. The link is enabled immediately in the view mode: Click to open the corresponding web page. 71 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Visualize plants...
  • Page 72 12. Modify Position and Scaling. 13. Click Apply to check the results of formatting in a preview. 14. If satisfied, click OK to finish. 15. Click OK to change to view. 72 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Visualize plants...
  • Page 73: Record Consumption Data

    … The OZW772… periodically queries consumption data. † You can view consumption data via web operation (local or remote) or have it send by e-mail. 73 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data 2015-10-12...
  • Page 74: Consumption Data File

    "Consumption data"). Web Server data Plant information relies on the Web Server and is mapped "ad hoc" when querying and sending the consumption data file. 74 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data 2015-10-12...
  • Page 75: Meter Data In Detail

    QAX9… or on the Synco 700 controller (not E and not F1) and then retrieved by Web Server. Note Data in the section on meter status (E) are specific to the manufacturer for M-bus meters. 75 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data 2015-10-12...
  • Page 76: Time Ratios

    · The KNX S-Mode values are transmitted by meters with COV to the OZW772… S-Mode à OZW772… · Current values, defined for a meter media, are taken over in the consumption data file daily between 5 and 10 am. 76 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data...
  • Page 77 · A due day value is used for precision only if one M-bus meters supplies a due day value on the centralized due day. 77 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data...
  • Page 78 · Change to data point type with ETS · Change to meter media with ETS · If the new value is less than the old value 78 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Record consumption data...
  • Page 79: Send Consumption Data File

    Exemption from liability The Siemens system for transmitting acquired consumption data for meters uses the latest technology and security standards. The value as displayed on the meter applies for allocation purposes in the event of differences between the displayed value on the meter and the value as transmitted.
  • Page 80: "Energy Indicator" Function

    · The data point is not monitored via the "Energy indicator" function. No tree leaf Standard EN 15232 The "Energy indicator" function is based on standard EN 15232 "Energy efficiency in buildings". 80 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 81: Knx Bus Topology

    OZW772.250 up to 250 bus devices via the "Energy indicator" function. Note A maximum processing time of ca. 8 hours results for a max. quantity of 2500 "Energy indicator" data points. 81 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 82: Synco Product Range

    The default values can be changed with a few notable exceptions. Neither number nor selection of the "Energy indicator" data points and "Green limits" that exist in the "Device description" can be changed. 82 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 83: Navigation And Device Web

    Path: Home > ... > Device web pages Note The "Device web pages" (see screenshot) pane can be opened with "Service" and "Administrator" access rights. 83 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 84: Energy Indicator" Function Levels

    Section 7.3.4. When a checkbox is cleared (deactivated), message "Monitoring off, green limits reset to default values! Really to be continued?" is displayed; see Section 7.3.4. 84 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 85: Partial Plants" Level

    Monitored data points Indication of the number of actively monitored data points (x) for possible number of data points to be monitored (y) for each partial plant; see Section 7.2.4. 85 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 86: Data Points" Level

    The dialog box (click red pen symbol ) shows all enumeration values. Note When level "Data points" is selected, they are sorted by "Device Description". Users cannot change the sort order. 86 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 87: Number Of "Monitored Data Points

    "x of y" is displayed for each partial plant in the corresponding row and the sum "Partial plants" level of all partial plants is displayed in the bottom row. Note Level "Data points" does not have indication "x of y". 87 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 88: Energy Indicator" Visibility

    "Energy indicator" remains active even if "Energy indicator on the web = Not visible" is selected. Configuration "Energy indicator on the web" (Visible/Not visible) also applies to user groups "Service" and "End user". 88 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 89: Summary Display "Energy Indicator" For A Plant

    The summary display "Orange leaf" with "2 Green limit(s) crossed" is displayed (in the previous example) because two "Green limits" were exceeded in "Controller 1" (see next screenshot). 89 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 90: Energy Indicator" Commissioning Function

    Device data point values are not transmitted if there is no bus supply or if the KNX bus is interrupted. No comparison to "Green limits" then takes place and column "Value" contains "---" while column "Energy indicator" displays a "Grey leaf". 90 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 91: Estimated Processing Time

    The checkbox in the "Energy indicator" column allows for deactivating monitoring of one or multiple data points e.g. for operational reasons. Data point monitoring active (default following commissioning) Data point monitoring deactivated 91 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 92 Following "Monitoring off" and reactivation, "Energy indicator" data points may no longer be within the green limits, as the "Green limits" reset to default values have different dependencies. 92 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 93: Activating "Data Point Monitoring

    Selecting the checkbox for partial plant "Room 2" activates it. As a result, all data points at the "Data points" level are also activated. Partial plant "Room 2" is reactivated. All data points of "Room 2" are reactivated. 93 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 94 Note that "Monitoring activated" at the "Partial plants" level does not mean that all subordinate data points are activated and monitored also. This also applies to "Monitoring activated" at the "Plant level". 94 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 95: Dialog Boxes, Data Points, And "Green Limits

    The "Green limit" slider is always "green/orange". If the slider is moved to the setting range limit value, the bar color disappears in the direction of the movement. 95 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 96: Dialog Boxes With Numeric Data Points

    Note Set the cooling setpoint by 1 K higher (or max. the same) as the "Green limit" to display the "Energy indicator" = "Green leaf". 96 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 97: Dialog Boxes With Enumeration Data Points

    Preselection operating mode Note The enumeration values are predefined as per the data point type. The "Green limit(s)" are set by clicking the selection boxes. 97 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 98: Dialog Boxes With Variable Unit Data Points

    The checkbox can be enabled with "Administrator" access rights. The "Green limit" can be set and the "Value" (data point value) is compared to the "Green limit". 98 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 99: Dialog Boxes For Data Points With Manually Set Value

    "Value" slider is hidden. The value can be set if the checkbox is selected . The value is then also compared to the "Green limit". 99 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function...
  • Page 100: User Groups "Service" And "End User

    Contrary to the "Administrator" user group, the dialog box "Preselection" contains operating mode grayed enumeration values (operating modes). User groups "Service" and "End user" thus can only read, but not change the set "Green limits". 100 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 101: E-Mail With "Energy Indicator" For The Plant

    · Reception is confirmed in data point "Energy indicator transmitted = Yes". · Data point "Reason" contains feedback on whether the e-mail was sent or which setting must be checked in the event of an error. 101 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 102: Mail Inbox

    · The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2. · Manually triggered "Test receiver" is successful. Note The diagnostic options are identical to those of other e-mail Receivers. 7.5.2 Mail inbox 102 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator" function 2015-10-12...
  • Page 103: E-Mail Contents

    The contents of the e-mails comprises (see screenshot below): contents · E-mail format Text only (see message field below). · E-mail sender As per the settings (e.g. ozw772@siemens.com). · E-mail Receiver As per the settings (e.g. first name.lastname@example.com). Reference field The Reference field comprises the following information: ·...
  • Page 104: Exceptions

    Changed data of the "Energy indicator" function are lost. The "Energy indicator" function starts with the data point values and "Green limits" similar to creating a device list in the Web Server. 104 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies "Energy indicator"...
  • Page 105: Communications

    All functions are available after the user also logs on to the portal and activates the plant. No further settings required on router. The workflow for accessing via the portal is described in Section 3.1 "Set up access via portal". 105 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 106: Access Via Local Area Network (Lan)

    For manual settings, use the PC to determine the required data. Procedure: Select Start > Control Panel > Network connections > Local Area Connection. Select "Support" tab. Click [ Details... ] 106 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications 2015-10-12...
  • Page 107 The Web Server's IP address can be set manually as an option. · We recommend using IP addresses from the private range in the home network (see Section 11.3.1). 107 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 108 Select Start > Control Panel > Network connections > Local Area Connection. Select the "General" tab. Click [ Properties ] Select "Internet Protocol (TCP/IP)". Click [ Properties ] Select "Use the following IP address". Continued on next page. 108 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications 2015-10-12...
  • Page 109 · Settings for the standard gateway and DNS servers are irrelevant in a local area network without a router. · We recommend using IP addresses from the private range in the home network (see Section 11.3.1). 109 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications...
  • Page 110: Access Via Direct Connection

    Internet, since it does not have a firewall. This is normally a component of the DSL router. · The examples here were created using the Siemens Gigaset SX763 router Notes Workflows, terms, and functions vary by product used, the principle remains the same for all products.
  • Page 111 We recommend enabling the firewall to protect the local area network: · Firewall: On Address translation Activate NAT to ensure that the Web Server can be reached via the Internet: (NAT) · NAT: On 111 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications 2015-10-12...
  • Page 112 In the example, queries from the Internet to a public IP address (Internet connection)/port 80 are forwarded to local IP address 192.168.2.10 (Web Server)/Port 80. Port 21 is also enabled for file transfer. 112 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications 2015-10-12...
  • Page 113 HTTPS encryption via port 443 is also supported. The required certificate is not (HTTPS) accredited. The self-signed certificate from Siemens is valid for 20 years and is installed on the Web Server. The certificate must be installed on the web browser for encrypted communications.
  • Page 114: Messages Via E-Mail

    · User settings are in bold. · The path for user settings starts each time with: Home > 0.2.252 OZW772.16 > Settings > … · Set components of the e-mail are in italics. 114 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Communications...
  • Page 115 Web Server fault Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subject: OZW772.16: Message central unit …> Texts: Name: Message type Device: OZW772.16 (0.2.252)
  • Page 116 Fault eliminated Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subject: OZW772.16: Message central unit …> Texts: Plant name: Message type Device: OZW772.16 (0.2.252) or...
  • Page 117 Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subject: OZW772.16: System report …> Texts: Plant name: Message type central unit...
  • Page 118 "User name" and "Password" from the mail server for each e- mail transmission. · The mail server can also be installed on the local area network. 118 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 119: Trend Functions

    Trend overview appears as follows if not trend has been defined: Trend overview appears as follows if trends have already been defined: An active trend is highlighted in green. 119 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 120: Define Trend

    You define trends on the trend overview page. 1. Click the red pencil to create or edit a trend. The Edit window opens. 2. Enter trend name. 120 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 121 As of OZW version 5.0, data points integrated in the system via KNX S-Mode (e.g. lighting, blinds, energy and volume measured values) are available to the trend function. 121 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 122 Missing data points are listed in the trend file (.csv) with a "?". The missing data points are displayed as a break in the curve for the trend graph. 122 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 123 "In process". T1-T5 Trend channel 1-5 and query interval XXmin Start time of trend Trend time for the corresponding data point 123 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions 2015-10-12...
  • Page 124: Restriction To Bus Load

    1. Click the red waste can symbol The confirmation window Delete of the trend data opens. 2. Confirm delete of trend data with OK. The trend settings and data is deleted. 124 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 125: Add Trend Data Points

    3. You can add a maximum of 100 data points to the trend using the plus symbol . Bus load and trend period is adapted to the number of data points accordingly. 125 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 126: Manage Trend Ram

    The read data is written first to RAM while trending. It is transmitted to Flash memory every 60 minutes. A maximum of one hour of trend data is lost in the event of a power outage. 126 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 127: Send Trend Data By E-Mail

    2. Click E-mail address of the desired receiver 1 or 2 or the red pencil symbol . The Edit window opens. 3. Enter the desired e-mail address. 4. Click OK to confirm. 127 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions 2015-10-12...
  • Page 128: Sent Transmission Options Per Trend Channel

    The window displays name, state, circular logging, transmit interval, and message receiver. Set transmit interval 1. Click Transmit interval or click the red pencil The edit window opens. 128 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions 2015-10-12...
  • Page 129 --- : No transmission of e-mails from this trend channel Receiver 1: Transmission to receiver 1 Receiver 2: Transmission to receiver 2 Receiver 1 + 2: Transmission to receiver 1 + 2 129 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 130: E-Mail Content And Appendix

    – Number and name of the trend channel – Query interval – Beginning – End (last trend item prior to transmitting trend data) – Path and data point name of trend 130 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions 2015-10-12...
  • Page 131: Download Trend File Via Web

    5. Confirm the selected period with OK. 6. The Export window may be displayed for larger amounts of trend data. The window is skipped for smaller files. 131 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 132 Click to download and is available at a later date. The next time a file is encoded, the link is replaced by the newer link. 132 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 133: Graphical Trend Display

    Display multiple trend Only one trend channel can be graphically displayed in each browser pane. channels Another browser pane required to display another trend channel simultaneously. 133 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions 2015-10-12...
  • Page 134: Import/Export Trend Definitions

    2. For the desired trend channel, click Import A request is displayed to delete existing trend data if the trend channel was previously used. 3. Confirm with OK. 134 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 135 In the display example, the address 0.2.230 is retained since it is an import within the same device. 12. You can check the settings for import in the following window and change as needed. 135 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 136 A trend definition can be copied as follows within the same OZW: within OZW 1. Export trend definition for the desired trend channel. 2. Import trend definition to another trend channel. 136 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 137: Acs Trend

    A trend created in OZW or as of ACS V9.01 cannot be edited or displayed with ACS V9.00 or older versions. Write trends defined in ACS via ACS to OZW (and not trend export/import). 137 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 138: Acs Trend Bus Load

    The trend automatically changes to the state established in the trend definition. Note The trend is only started for a trend definition of "Running" if the resulting overall bus load does not exceed 100%. 138 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Trend functions...
  • Page 139: Knx S-Mode

    Data points recording by OZW can be used, for example, for trending, to depict the plant diagram or to calculate thermal or electrical energy consumption. Example for showing KNX data points in a plant diagram: 139 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 140 System mode (communication mode in KNX networks). Additional information Addition information on KNX and Synco devices with S-Mode data points can be found in document CE1Y3110. 140 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 141: 10.1 Configuration In Knx S-Mode

    An update takes up to 70 second for 237 S-Mode data points on the same page. We recommend grouping the data points in a logical manner and spreading them out over various pages. 141 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 142 · Lighting, blinds, temperature values, energy values, etc. Example Page names in ETS4/ETS5 Page names in OZW772… ETS issues an error message if you exceed the maximum entry length of 20 characters. 142 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 143 · Energy consumption heating Data points in ETS4/ ETS5 Example Data points in OZW772… ETS issues an error message if you exceed the maximum entry length of 36 characters. 143 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 144 A total of 237 data points are available, together with 7 standard data points (data point numbers 1…7). ID/Name/Decoding Each data point sub-type has an ID, a name, and a specific selection of possible settings (decoding). 144 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 145 · A name is assigned to a data point in the field "data point name", e.g. instead of the default name "Data point type/one-up number" · A meaningful name such as 145 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 146 Uneven values are used for "edit"; even for "display". Available settings for the data point type: Data point numbers 48…67: "Change value 1…20" Available settings for the data point type: 146 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode...
  • Page 147 Data point numbers 88…107: "Display value 1…20" Available settings for the data point type: 2 bit data points Data point numbers 108…112: "Switching controlled 1…5" Available settings for the data point type: 147 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 148 1 byte data points Available settings for the data point type: Data point numbers 133…152: 1 "Value change+display 1…20" Available settings for the data point type: 148 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 149 The field "Scene number" defines which scene number [1…64] is affected by the command. Data point numbers 158…177: "Display value 1…20" 2 byte data points Available settings for the data point type: 149 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 150 Data point numbers 178…197: "Value change+display 1…20" Available settings for the data point type: 4 byte data points Data point numbers 198…237: "Display value 1…40" Available settings for the data point type: 150 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 151 Displays (state, e.g. room temperature) C W T U Send (trigger, e.g. light switch) Send + display (state + trigger, e.g. heating setpoint). C R W T U 151 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 152 First, select the desired room unit (QMX3.P37) from the device list. Left click data point "1: Room temperature [°C] – Transmit" to drag it to the empty pane. 152 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode...
  • Page 153 Web Server. In this case, page 2, which was defined as the living room when the page name was issued. The data point is now dragged to the group address: 153 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 154 When ETS is connected to the KNX bus via OZW, ETS has the KNX address 15.15.254. By configuring the OZW with ETS, the default group addresses are overwritten by system time and faults. 154 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode...
  • Page 155 · Writing and entire project · Write a project without changes · Add / delete /rename KNX pages. · Add /Delete /Change type/Rename data points. 155 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 156: Operation Knx S-Mode

    The value is sent over the bus to the defined S-Mode address by clicking the value and confirming it with "OK", even if the value has not changed. "Cancel" cancels the operating dialog and not value is sent over the bus. 156 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 157 "OK", even if the actual value was not adjusted. Heartbeat Communication on and over the KNX bus is event-controlled. The data points have no heart beat as a rule. 157 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode...
  • Page 158 Scene control: Call up/memorize scene number) 20.* 20.002 Building mode (building operating mode: Building used, building not used, building protection) * = unsupported subtype from this main type group 158 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies KNX S-Mode 2015-10-12...
  • Page 159: Appendix

    * Device failure (bus) is a fault generated by the Web Server for a failed device. As result, the device failure (bus) is assigned to "System faults", whereas all other faults generated by the Web Server are assigned as "Local faults". 159 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 160: 11.2.2 Windows Commander

    Check whether DNS and mail servers can be reached. nslookup <IP address> Translates an IP address to the domain name and or <domain> vice versa: Look up domain names. 160 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 161: Communications

    TLS required Yahoo! Mail smtp.mail.yahoo.com 25, 587 Additional information on free e-mail providers: · http://www.patshaping.de/hilfen_ta/pop3_smtp.htm · http://www.iopus.com/guides/bestpopsmtp.htm Note Siemens is not responsible for the content of external pages. 161 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 162: 11.3.3 Install Rndis Driver

    Wait until installation is complete and click [ Finish ] Result The RNDIS driver is now installed. The PC can communicate with the Web Server via USB. 162 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 163 Result The RNDIS driver is now installed. The PC can communicate with the Web Server via USB. Note The RNDIS driver is installed as part of the ACS790 Siemens software installation. 163 / 176 Siemens Web server OZW772... V6.0 CE1C5701en...
  • Page 164: 11.3.4 Alternative Network Configuration

    Enter IP address, subnet mark and operational standard gateway as well as DNS server. Result The PC assumes the configuration with these settings as soon as it is no longer integrated in the standard network. 164 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 165: Glossary Of Ethernet And Internet Terms

    DSL is a type of data transmission allowing for 1.5 Mbps access to the Internet on standard copper phone lines. The Internet Service Provider ISP provides the DSL connection. You need a DSL modem for this type of connection. 165 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 166 The Web Server supports HTTPS (Hyper Text Transfer Protocol Secure). A hub in a star-topology network connects various network devices by receiving all data from one device and forwarding it to other devices. 166 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 167 48 bit, e.g. 00-55-96-5D-00-2C. The MAC address is assigned by the network adapter manufacturer and cannot be changed. Mbps Million bits per second indicates the transmission rate in a network. Media Access Control see MAC address. 167 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 168 Internet (without a need for a public IP address). Port Forwarding is achieved by the correct NAT / PAT definition in the router. Protocol for dial-up connection of a computer to the ISP. PPP over Ethernet See PPPoE. 168 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix 2015-10-12...
  • Page 169 A default gateway (see Default Gateway as well as DSL router) is also referred to as a network address used by clients to send their packages if the target address is outside the immediate network. 169 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies...
  • Page 170 (application). UDP, in contrast to TCP, is an unsecured protocol. UCP is a so-called connection-less protocol. Data packets are broadcast. The Receiver is responsible for receiving data. The sender does not receive notification if the data packages were received. 170 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Appendix...
  • Page 171 In addition, they automatically provide, depending on class, own services or use services of other devices on the network. A URL refers to an information source, e.g. http://www.siemens.com. The URL is a uniform web address that is used to determine the network protocol used (e.g.
  • Page 172: Index

    Internet protocol ..........161 Mailbox ............102 Private networks ..........161 Remote operation .......... 105 E-mail Trend receiver ........127 Energy indicator Consumption data ..........32 COV ..............157 Green leaf ............80 172 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Index 2015-10-12...
  • Page 173 Page display in OZW ........156 Port forwarding (PAT) ........112 Pages ............142 Portal Plant diagram ........139, 157 Access ............44 Project data ........... 154 Log in .............. 46 173 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Index 2015-10-12...
  • Page 174 Synco range ............82 Language ............24 System data update ..........43 Web Server diagnostics ........53 System report Web Server settings ..........23 Message cycle ..........31 Windows Commander ........160 174 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Index 2015-10-12...
  • Page 175 175 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies Index 2015-10-12...
  • Page 176 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 © Siemens Switzerland Ltd, 2009 www.siemens.com/buildingtechnologies Subject to change 176 / 176 Siemens Web server OZW772... V6.0 CE1C5701en Building Technologies 2015-10-12...

Table of Contents