How To Set And Add The Smoke Detector (Connected To The Ai/Di Port On The Rack Environment Unit) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
2.
3.
Step 2 Check the monitoring functions of smoke sensor.
Table 8-23 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End
8.1.8.29 How to Set and Add the Smoke Detector (Connected to the AI/DI
Port on the Rack Environment Unit)?
If a smoke sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the network cable has been stripped, core wires 1, 5 and 8 have been
short-circuited, core wires 3 and 6 have been connected to the cable delivered with the smoke
detector, and the other end of the network cable has been connected to the AI/DI port on the
rack environment unit.
Context
Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
4.
Step 2 Check the monitoring functions of smoke detector.
Issue 05 (2019-09-16)
Choose Monitoring > Aisle > Skylight Actuator Group > Skylight Actuator 1 >
Running Parameters > DI1 alarm level.
Set DI1 alarm level to Low voltage alarm or High voltage alarm, and click Submit.
Set DI1 alarm level to Low voltage alarm if the smoke sensor is connected over NO.
Set DI1 alarm level to High voltage alarm if the smoke sensor is connected over NC.
Normal Connection Status
DI1_smoke alarm is displayed
on the active alarm page of the
app or WebUI.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the smoke sensor is connected to the AI/DI_1 port on the rack environment unit.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Cabinet > IT Cabinet n > Cabinet Collector n > Running
Parameters.
In AI/DI_1 Port Settings area, set AI/DI_1 sensor to Enable, click Submit.
Set AI/DI_1 sensor type to Smoke sensor, click Submit.
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
Press the reset button of the
smoke sensor to clear the alarm.
8 FAQ
217