How To Set And Add The T/H Sensor (Bom Number: 02310Nbs) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Table 8-32 Function check
Check Method
Check the running information
about the T/H sensor on the
WebUI.
Set T/H sensor alarm thresholds.
----End

8.1.8.36 How to Set and Add the T/H Sensor (BOM Number: 02310NBS)?

If a T/H sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port on the T/H
sensor, and the other end has been connected to the COM port on the ECC800.
Procedure
Step 1 Set the T/H sensor device address.
Set the T/H sensor device address through the DIP switch on the T/H sensor.
Toggle switches 1 to 6 of the DIP switch specify the device address in binary mode. ON
indicates 1, and OFF indicates 0.
Table 8-33 Setting a device address
Address
1
2
3
4
Step 2 Add a T/H sensor.
Issue 05 (2019-09-16)
Toggle
Toggle
Switch 1
Switch 2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Info, and check the current
T/H information of the cabinet.
Choose Monitoring > Aisle > T/H Sensor Group >
T/H Sensor n > Running Parameters, and set High
temperature alarm threshold, Low temperature
alarm threshold, High humidity alarm threshold,
and Low humidity alarm threshold as required.
NOTE
The default values of High temperature alarm threshold,
Low temperature alarm threshold, High humidity alarm
threshold, and Low humidity alarm threshold are 30.0° C,
5.0° C, 85.0% RH, and 15.0% RH, respectively.
Toggle
Toggle
Switch 3
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
8 FAQ
Toggle
Toggle
Switch 5
Switch 6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF