7.5.6
Status Screens
DESCRIPTION
1
Load is protected by UPS power. Load is supplied by inverter
(Normal Operation) and the batteries are connected and are OK.
2
Load is not protected by UPS power. Load is supplied by mains
power (load on bypass) or it is supplied by the inverter (normal
operation) and the batteries are not OK.
3
Load not supplied. UPS is switched off.
To start the UPS press the two ON/OFF buttons simultaneously.
4
The UPS/module is not supplying load anymore. The output
switch is open.
S
stands for Single UPS. The system consists only of one UPS.
P01 stands for Parallel UPS in a Multi- UPS system and 01 stands for the first UPS (MASTER) in the parallel UPS system.
P02 stands for Parallel UPS in a Multi- UPS system and 02 stands for the second UPS (SLAVE) in the Multi- UPS system.
P03 stands for Parallel UPS in a Multi- UPS system and 03 stands for the third UPS (SLAVE) in the Multi- UPS system.
The definition of the UPS "Position" in a parallel system is achieved in the Menu Set-Up Service.
DESCRIPTION
Single UPS Systems
Parallel System e.g. first UPS cabinet
Parallel System e.g. second UPS cabinet / Slave
Note: The max no. of UPS units is 6.
7.5.7
Main Menu Screen
DESCRIPTION
1
Logging Control. A log of the last 99 events is stored in the
Power Management Display.
2
In Menu Measurements: monitor voltages, power, frequencies,
currents, autonomy etc.
The Command Menu is where to perform the commands "Load
3
to inverter", "Load to bypass", "battery test".
The UPS Data are the UPS personalized information "serial
4
number"
5
Various settings can be performed by the user: Date/Time,
automatic battery test, etc.
6
Various adjustments can be performed by the service staff
SW1-9
Single cabinet
1
ON
2
ON
3
ON
4
OFF
5
ON
6
ON
7
OFF
8
OFF
9
ON
Table 12: DIP Switch SW1-9
LCD-DISPLAY
SYSTEM CONFIGURATION
SINGLE
SYSTEM CONFIGURATION
PARALLEL
LOAD OFF
SUPPLY FAILURE
LCD-DISPLAY
LOAD
PROTECTED
LOAD
NOT PROTECTED
LOAD OFF
SUPPLY FAILURE
LOAD DISCONNECTED
PARALLEL SWITCH OPEN
LCD-DISPLAY
EVENT LOG
MEASUREMENTS
MEASUREMENTS
COMMANDS
COMMANDS
UPS DATA
UPS DATA
SET-UP USER
SET-UP USER
SET-UP SERVICE
SET-UP SERVICE
NO MORE MENU
Conceptpower DPA 500 480V UL │94-12-043275 A02 41
P01
P01
P01
P01
S
P01
P02