CABLES BETWEEN BATTERIES AND THE UPS SHOULD BE RUN IN MATCHED PAIRS, POSITIVE-
WITH NEGATIVE, WITHIN EACH CONDUIT OR CABLE RUN.
GROUPING LIKE-POLARITY CABLES TOGETHER, FOR EXAMPLE, POSITIVE-WITH-POSITIVE AND
CAUTION
NEGATIVE-WITH-NEGATIVE, CAN CAUSE STRESS OR DAMAGE TO THE CABLES, CONDUIT OR
BUSWORK.
To ensure protection of service personnel during the UPS installation, make sure that the connections are performed under the following
conditions:
 No mains voltage is present in the UPS
 All loads are disconnected
 The UPS and external battery are voltage-free
To verify the complete shutdown of the Conceptpower DPA 500 perform following steps:
 No mains voltage is present
 All loads are shut down and disconnected
 UPS is shut down and voltage-free
 All 5x parallel Isolators CB1-1, CB1-2, CB1-3, CB1-4, CB1-5 are in position OFF (open)
 All 5x battery breakers CB2-1, CB2-2, CB2-3, CB2-4, CB2-5 are in position OFF (open)
 Verify external battery circuit breakers/fuses in the external battery cabinet are open.
5.7.1

Installation Checklist

All packing materials and restraints have been removed from each cabinet.
Each cabinet in the UPS system is placed in the installed location.
All conduits and cables are properly routed to the UPS and auxiliary cabinets.
All power cables are properly sized and terminated.
A ground conductor is properly installed.
If the cabinet does not use all module mounting locations, the provided dead fronts are installed on the front of the cabinet.
Battery cabinet installation instructions have been completed.
Air conditioning equipment is installed and operating properly.
The area around the installed UPS system is clean and dust-free. (It is recommended that the UPS be installed on a level floor
suitable for computer or electronic equipment.
Adequate workspace exists around the UPS and other cabinets.
Adequate lighting is provided around all UPS equipment.
Any optional accessories are mounted in their installed location and properly wired.
Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
Startup and operational checks performed by certified service personnel.
22 Conceptpower DPA 500 480V UL │94-12-043275 A02