Operating Mode - ABB Conceptpower DPA 500 User Manual

480v ul – modular ups, 100kw – 3 mw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

User
This menu enables the user to program battery tests and to configure operations using generators. It also allows to set the time and date
and the selection of the language of the display.
Service
This menu is reserved for certified service engineers. It is not to be used by end users and is protected by a password.
UPS Measurements
Output Voltage (V)
Output Current (A)
Output Frequency (Hz)
Output Power (%)
Active Power L1 (kW)
Active Power L2 (kW)
Active Power L3 (kW)
Reactive Power (kVAr)
Apparent Power (kVA)
Inverter Voltage (V)
Bypass Voltage (V)
Bypass Frequency (Hz)
Rectifier Voltage (V)
Rectifier Temperature (
Inverter Temperature (
Udc Gain +
Udc Gain -
Upgrading from LCD to Graphical Iinterface
For substitution of past generations displays, certify that the UPS software version is compatible with the graphical display. If that is not
the case, upgrade the system to the newest software version. Then substitute the entire door of the UPS and connect the display using
the same connector as for the LCD control panel. All information from the UPS (such as serial number, manufacturing date and version
of the software and hardware) will be automatically loaded to the new interface once it is connected to your UPS.
7.4.7

Operating Mode

7.4.7.1
Online Mode (Inverter Mode)
The Online mode is the UPS operating mode in which the load is supplied through the rectifier and the inverter.
User Settings
Language
Date
Time
Battery Test
Repeat Test
Generator Operation
Battery
Run Time
Voltage + (V)
Voltage - (V)
Charge Current (A)
Discharge Current (A)
o
Temperature (
C)
I Battery Offset
Capacity(%)
V Battery Offset +
V Battery Offset -
Autonomy (min)
Type
Blocks
o
C)
Cells
o
C)
Floating Voltage (V)
Minimum Threshold
Common Battery
Start Fast Charge
Stop Fast Charge
UPS Data
Manufacturing
Firmware Version
Hardware Version
Display Version
Dynamic Password
Figure 20: Online Mode on Mimic Diagram
Offset
P Load Offset L1
P Load Offset L2
P Load Offset L3
Q Load Offset L1
Q Load Offset L2
Q Load Offset L3
Inverter DC L1 Inverter DC L2
Inverter DC L3
Output DC L1 Output DC L2
Output DC L3
I Inverter Offset L1 I Inverter Offset L2
I Inverter Offset L3
I Bypass Offset L1 I Bypass Offset L2
I Bypass Offset L3
I Battery Offset
V Battery Offset + V Battery Offset -
Commands
Tests
Clear Alarms
Inverter Voltage
Service Mode
Open K Bypass
Standby Mode
Close K Bypass
Default Config.
UPS
Type
Power
Unit Number
Slot ID
Cosphi
System
Parallel
Frequency
Sync Window
Inverter Voltage (V)
Rectifier Voltage (V)
General Alarm Delay
Converter
Separate Bypass
Conceptpower DPA 500 480V UL │94-12-043275 A02 37