Pin Assignments of the IndraControl VCH 08.1
DANGER
The DC 24 V input voltage must comply with the requirements of the
"Protective separation"!
Plug and unplug the connector only if there is no voltage!
Fig.7-16:
Safety transformer according to EN 60742
Interfering AC voltage components such as the ones resulting from an uncon‐
trolled three-phase bridge circuit without smoothing and with a ripple factor (see
DIN 40110/10.75, section 1.2) of 5 % are allowed.
That results in the greatest absolute value of 30.2 V as upper voltage limit. The
lowest obsolete value of 18.5 V is the lower voltage limit.
Fig.7-17:
Limit values of the DC 24 V voltage
DOK-SUPPL*-VCH*08.1***-PR02-EN-P
Rexroth IndraControl VCH 08.1 Hand-held Terminal
Danger without protective separation!