Pin Assignments of the IndraControl VCH 08.1
Cable routing RS-232-C, black
RJ-45 connector
Opening the cable chamber.
Place the IndraControl VCH 08.1 on an even and clean sur‐
face with the display facing upwards so that the IndraControl
VCH 08.1 or its operating elements are not damaged (e.g.
ESD mat).
Use a Philips screw driver (size 2) to open and close the cable
chamber.
Modifications in the cable chamber:
When disconnecting the main connector (S22) please ensure
that the connector is disconnected by pulling at its core (do not
use any pointed devices).
When disconnecting the RJ-45 connectors (S11 or S4) please
make sure that the locking lever is pressed.
Fig.7-2:
NOTICE
Ensure that the S22 and S4 / S11 connectors correctly snap in when you plug
them in.
NOTICE
Advice on closing the cable chamber:
The seal must be clean and intact and be situated at the correct position
in the cable chamber cover.
No cables may be clamped.
The cable chamber cover must be screwed on using all 6 screws (torque:
0.4 to 0.5 Nm). Otherwise the protection degree cannot be guaranteed.
The following figure shows the cable routing using the RS-232-C interface.
DOK-SUPPL*-VCH*08.1***-PR02-EN-P
Rexroth IndraControl VCH 08.1 Hand-held Terminal
Possible malfunctions due to incorrectly snap‐
ped in connectors.
Possible malfunctions due to incorrectly closed
cable chamber.