ESIE15-13B
4.39 Transmission Error Between Centralized Controller and
Indoor Unit
UE
Remote
Controller
Display
All models of indoor units
Applicable
Centralized controller
Models
Schedule timer
Micro-computer checks if transmission between indoor unit and centralized controller is normal.
Method of Error
Detection
When transmission is not carried out normally for a certain amount of time
Error Decision
Conditions
Transmission error between centralized control and indoor unit
Supposed
Defective PCB for central remote controller
Causes
Defect of indoor unit PCB
Breaking and wrong wiring of connecting wire
Failure of the setting of group No. and address
Service Diagnosis
Troubleshooting by Remote Controller
181