Page 8
17.2 Serial Hall Lantern Hall Board Status ................134 17.3 Errors ........................135 17.4 Hall Lantern Masks ....................135 C4 Data Acquisition Device (D.A.D) Unit ............. 136 18.1 Wireless Connection to D.A.D Unit ................136 18.2 Uploading Revision Board Software ................136 18.3 Troubleshooting ......................
• C4 Testing Procedures – Step by step procedure on how to test the C4 Traction Controller. • C4 Drive Startup – Describes how to setup various drives that may be used within the C4 Traction Controller. The following is a list of drives that can be used on the C4: •...
This is done to protect the equipment from overvoltage issues. For example, the door operator for that job might operate at 240 VAC but if Smartrise was not provided with that information when the job was developed, the DR breaker (door operator voltage supply) is set to 120 VAC for safety reasons.
C4 User Manual REF Terminal – A shield connection to connect to the drive, as applicable. See the C4 Controller sheet 02 Machine Room I/O for wiring information. 2.6 Network The network is used for board to board communication between the Machine Room, Car Top, Car Operating Panel and Expansion boards.
THE CONTROLLER BEFORE WIRING THESE TERMINALS. Safe Terminal – Outputs power to the motor contactor. The safe terminal will not output voltage to the motor contactor coil until all safety checks have been completed. See C4 Controller sheet 02 Machine Room I/O for wiring information.
24 VDC output is labeled 601-608. Each output sinks to REF when activated. LEDs 601-608 are lit when active. See the C4 Controller sheet 02 Machine Room I/O for wiring information. Figure 16: 24 VDC Output Connector 2.9 24 VDC Monitoring System The monitoring connector is used to monitor the system.
ALL CONNECTIONS ON THIS TERMINAL BLOCK ARE HIGH VOLTAGE. DISCONNECT POWER TO THE CONTROLLER BEFORE WIRING THESE TERMINALS. The following input terminals. See the C4 Controller sheet 02 Machine Room I/O for wiring information. ATU Terminal – Access Top Up controller termination ATD Terminal –...
Page 72
Day of the month the C4 is set for monthly automatic load recalibration Monthly Calib. Hour Time of the day the C4 is set for monthly automatic load recalibration Trigger Recalibrate When set ON, the car performs a load weighing device...
All connections regarding safety are functional during Construction mode. Perform the following procedure on how to connect the MR Board prior to beginning the Construction mode. See the C4 Controller sheet 04 Motor and Drive Connections for wiring information. Connect a jumper from L120 to terminals LFT, LFM, and LFB.
4.3 Brake Board Settings Smartrise sets the brake pick and hold settings in the factory prior to shipping. Prior to running, verify the data. For the default or factory set data. See the C4 Controller sheet 01 Getting Started. The following table lists an example of the Data Settings.
The setup to run the controller in Construction mode is dependent upon the drive that is being used. Follow the steps in the C4 Drive Startup Manual for completing the motor tune operation. If the elevator is running at slow speed after completing all the Construction mode setup, usually 10 fpm, then the drive is in NTSD operation and needs to be disabled while on Construction mode.
Prior to running on inspection operation, all connections need to be made from the MR to the CT and CT to COP. See the C4 Controller sheet 02 Machine Room I/O, sheet 07 Traveler/Safety String, sheet 08 Car Board I/O, and sheet 09 COP Connections for wiring information.
MR board. To use this form of inspection, the car must be at a terminal landing. 5.2 Inspection Run Options and Adjustments Th C4 controller uses pattern generation to conduct all runs, including inspection runs. This means that there is an inherent ramp up to the inspection speed when beginning the run and a ramp back to zero speed when the run is released.
• Adjust run timers Pre-Torque Adjustments For jobs with the Smartrise serial load weigher device (LWD), load information can be used to provide pre-torqueing of the motor to accommodate for load changes and prevent rollback. See section 25.1 Calibration for calibrating the LWD.
Riser board. Both networks are terminated as described in example 1. NOTE: For most C4 PCB boards, a jumper is used to terminate the CAN bus. For Hall boards, the termination is set by switching DIP 10 to ON.
Scroll right and press Save. 16.8 Compatibility The V2 Hall board and C4 Hall board are NOT compatible. The C4 Hall boards have serial numbers starting in SR1060 and have 10 or 12 DIP switches, while V2 Hall boards have 8 DIP switches.
C4 User Manual 18 C4 Data Acquisition Device (D.A.D) Unit Each Smartrise C4 Controller comes wired to a D.A.D unit that comes equipped with a Graphical User Interface Application (GUI). The following section explains how to connect wirelessly to the D.A.D unit and access its application using a laptop or a tablet.
C4 User Manual 19 Assigning Inputs and Outputs Like previous Smartrise controllers, the C4 retains the ability to change, add, remove, or move inputs and outputs if they are not fixed (inputs/outputs that cannot be changed due to safety issues). Any UNUSED input or output can be assigned a feature if the installer needs additional features or needs to move an input or output.
The rescue operation safely and securely moves the car to the nearest floor and allow the passengers to exit if the car ever loses power. The Smartrise C4 Controller uses two forms of rescue: • Auto Rescue – The Auto Rescue is ON and has been implemented into the system (Done on the Engineering Data Forms).
If the torque scaling is being adjusted on the drive go to step 143. b. If the torque scaling is being adjusted on the C4 system go to step 144. Adjust the torque scale on the drive until the torque is just high enough to eliminate rollback.
25.1 Calibration steps 11-13. 25.3 Monthly Recalibration The C4 system can automatically be set for monthly calibration. This causes the empty load to automatically be relearned once a month on a specified day and time. The calibration is performed on the first occurrence of the configured day once a month.
Need help?
Do you have a question about the C4 and is the answer not in the manual?
Questions and answers