baltur TBL 85P Manual User Instructions page 10

Forced air burners of liquid, gaseous and mixed fuels
Table of Contents

Advertisement

Available languages

Available languages

PIPES FOR LIGHT OIL BURNER MODEL TBL 130P/ P DACA - 160P/ P DACA - 210P
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
PUMP AXIS
N.B. For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift. For each bend or valve deduct 0,25 m.
0006081325_201210
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
1 Tank
3 Wire-net filter
H
meters
4 Pump
6 Suction pipe
0,5
7 Return pipe
1
10 Bottom valve
1,5
2
2,5
3
3,5
10 / 28
Total meters
meters
Ø i. 16 mm.
40
45
45
50
50
Total meters
meters
Ø i. 16 mm.
40
45
45
50
50
P = 3,5 m. (max.)
Total meters
meters
Ø i. 14 mm.
Ø i. 16 mm.
36
55
30
48
25
41
20
32
15
24
10
15
4