2. Select File > Export Datalogger Program then select the data logger you will be connecting
the VOLT 100 series to. For this example, we'll select GRANITE 6.
3. By default, the CRBasic program will be saved in
C:\Users\username\Documents\SURVEYOR.
6. Programming quickstart
using Short Cut
Short Cut is an easy way to program the GRANITE data acquisition system to measure a sensor
and assign wiring terminals. Short Cut is available as a download from
https://www.campbellsci.com/shortcut. It is also included in installations of LoggerNet and
RTDAQ.
The following procedure shows using Short Cut to program the data logger to measure a type-T
thermocouple on a VOLT 100 series.
1. Open Short Cut and click Create New Program.
2. Double-click your GRANITE data logger.
3. In the Available Sensors and Devices box, start typing GRANITE. You can also locate it in
the Devices folder. Double click the GRANITE Measurement Module you are working with.
Type the serial number located on the VOLT 100 series label. Optionally, type a name in the
Module ID String if you want the module to have an ID. This is useful when multiple VOLT
100 series modules are connected to the GRANITE data logger.
VOLT 100 series