11. COMMISSIONING SCREENS

All those parameters displayed in the V5 are organised in various groups (G1 to G16). By pressing the "*" key it is
possible to open each individual screen group.
R RUN 800A 380V

G1 MENU OPTIONS

1 LOCK PARAM=NO
2 PASSWORD=0
3 WRONG P/W=XXXX
4 LANGUE=ENGLISH
5 INITIALISE=NO
6 COMMISSION=YES

G2 NAMEPLATE

1 ISTARTER=_ _ _A
2 I MOTOR=_ _ _ _A
3 V MOTOR=2
4 P MOTOR=_ _ _Kw
5 COS PHI M=85%
6 FREQ=50Hz

G3 PROTECTIONS

1 PHASE SEQUEN=2
2 OV LOAD=800A
3 OV/LOAD T=5
4 OVL FAC=100%
5 MOTOR PTC=NO
6 UNLOAD=0.0A
7 UNLOAD T=0FF
8 SHRPIN=OFF
9 ASYM I ENAB=Y
10 UNDER V=320V
11 U/V DELAY=5s
12 OVERVOLT=440V
13 O/V DELAY=5s
14 START LIMIT=3
POWER ELECTRONICS V5 Operation Instructions
32
RANGE
YES/NO
OFF, 000 to 9999
0000 to 9999
ENGLISH
ESPANOL
DEUTSCH
YES/NO
YES/NO
7, 17, 30, ...1600
1 to 1600
1 220_240
2 380_440
3 460_525
4 660_690
4 to 999
40% to 99%
50 Hz
50Hz/60Hz
1 NO SEQ PROTECT
2 L1 L2 L3 SEQ
3 INVERSED SEQ
0,6 to 1,5 x In
1 to 10
100 to 500%
YES/NO
0 to 0,9 x In
0 to 99 s, OFF
0,6 to 1,2 x In, OFF
YES / NO
162 to 208V @ 220V
280 to 360V @ 400V
350 to 450V @ 500V
508 to 653V @ 690V
0 to 10, OFF
231 to 266V @ 230V
400 to 460V @ 400V
500 to 575V @ 500V
726 to 835V @ 690V
0 to 10 s, OFF
1 to 10
15 STR/ INT=15Min

G4 ACCELERATION

1 STR DELAY=0s
2 PULS TORQ=50%
3 PULS TQ T=OFF
4 INIT TORQ=35%
5 INIT TQ T=1s
6 ACEL TIME=6s
7 I LIMIT=2800A

G5 DECELERATION

1 FREWEL STP=YES
2 DECL TIME=12s
3 DEC MD SEL=1
4 HAMR FACT=75%
5 MINI TORQ=1%

G6 INPUTS

1 OPER MODE=1
2 LOCAL RESET=Y
3 DINPUT1 SEL=4
4 DINPUT2 SEL=0
5 DINPUT3 SEL=0
6 DINPUT4 SEL=0
7 DINPUT5 SEL=0
8 ANI1 FORMAT=1
9 AI1 RANGE 0_10
10 AI1 UNITS=OFF
11 ANI2 FORMAT=1
12 AI2RANGE 0_10
0 to 60 Min., OFF
0 to 600
50 to 100%
0,1 to 0.9, OFF
30 to 99%
0 to 10
0 to 180
1.5 to 5 x In
YES /NO
1 to 180
1 NORMAL CURVE
2 HAMMER PREVENT
1 to 99%
1 to 99
0 DISABLE
1 LOCAL
2 REMOTE
3 SERIAL COMMS
4 LOCAL JOG L/S
5 PUMP CTRL-1
YES/NO
0 UNUSED
1 START
2 STOP PUSH BUTON
3 STOP-RESET N/C
4 START-STOP N/O
5 RESET N/C
6 LOW SPEED (+)
7 LOW SPEED (-)
8 DC BREAK
9 DUAL SETTING
10 EXTERNAL TRIP
0 0_20mA
1 4_20mA
2 0_10V
0 to 999
Bar, ºC, m
0 0-20mA
1 4-20mA
2 0-10V
0 to 999