Mandik FDMC General Information Manual page 9

Hide thumbs Also See for FDMC:
Table of Contents

Advertisement

TPM 083/12
3.3.
BKS 24-1B communication and control device is used for control and checks of fire dampers with
the BFL 24-T-ST actuating mechanism in conjunction with the BKN 230-24 supply and
communication device. BKS 24-1B receives information about the situation of the fire damper
through the BKN 230-24 supply and communication device and issues controlling commands.
The device is intended for building in into the distribution board. Light diodes on the front side of
the device indicates the operating situations of the damper and breakdowns of the whole system.
Tab. 3.3.1. Communication and Control Device BKS 24-1B
Communication and Control Device
Nominal voltage
Power consumption
Dimensioning
Protection Class
Degree of protection
Ambient Temperature
Connection
Fig. 8
Communication and control device BKS 24-1B
conection can
be interchanged
Notice: Relay contacts are drawn
Signals and diagnosis
light diodes
open
closed
closed
open
closed
closed
closed
closed
flashing
open
AC 24 V
~
Connection through
an insulation
Reset
Test
External buton
2-conductor wiring
to BKN230-24
without power
contacts
state
alarm
6
3
Power supply AC 24V
closed
closed
Check test cca 35sec, starting with switching AC 24 on or pressing
open
open
6
3
«Reset/Test» button
Current failure, possible cause: • short circuit or interruption of 2-conductor wiring
or damper failure (at BKN..) • Power supply AC 230V missing • defective
closed
6
3
flashing
thermoelectrical starting • smoke detector activated • exceeded operation time
• damper blocked
Failure saved in memory • Fault in system signalled, system check should be
closed
open
6
3
done
Damper (drive) turning into the direction of breakdown position
closed
6
4
flashing
Damper (drive) in breakdown position
open
closed
6
4
Damper (drive) turning into the direction of operating position
closed
closed
6
7
6
Damper (drive) in operating position
closed
closed
7
2,5 W (operating position)
III (safe small voltage)
Into ZSO-11 connector which is not a part of BKS 24-1B.
ZSO-11 connector has screw terminals 11 x 1,5 mm
BKS24-1B
transformer
2
AC
24V
10
Control
switched
on /off
1
5
optional
a
9
b
11
Reset
Test
Description
Cause/Course
not available
8
BKS 24-1B
AC 24 V 50/60Hz
5 VA
IP 30
0 ... + 50 °C
6
damper position
4
breakdown
3
failure
damper position
7
operation
8
open
closed
alarm
2