Check of blade displacement into the breakdown position "CLOSED" can be done after cutting
off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical
starting mechanism BAE 72B-S or cutting off the supply from ELECTRICAL FIRE
SIGNALISATION). Check of blade displacement back into the "OPEN" position can be done after
restoration of power supply (e.g. By releasing the RESET button or restoration of supply from
ELECTRICAL FIRE SIGNALISATION).
15.2.
Manual operation
Without power supply, the damper can be operated manually and fixed in any required position.
Release of the locking mechanism can be achieved manually or automatically by applying the
supply voltage.
15.3.
It is recommended to provide periodical checks, maintenance and service actions on Fire
Equipment by Authorized persons schooled by Producer.
15.4.
All effective safety standards and directives must be observed during fire damper assembly.
VIII. DATA OF THE PRODUCT

16. Data label

16.1.
Data label is placed on the casing of fire damper.
Fig. 27 Data label
FIRE DAMPER FDMC
CLASSIFICATION:
SIZE:
SERIAL NUMBER:
TPM083/12

17. Quick review

Tab. 17.1.1. Quick review
Damper
Size
Fire separating construction
Solid wall construction
Gypsum wall construction
Solid ceiling construction
EI 60 (ve ho i
Certificate:
1391-CPR-0090/2014
Wall/Ceiling
Installation
Min. thickness [mm]
100
Mortar or gypsum
100
Stuffing box with fire protection mastic
100
Mortar or gypsum
100
Stuffing box with fire protection mastic
150
Mortar or gypsum
150
Stuffing box with fire protection mastic
25
MANDÍK, a.s.
Dobříšská 550
267 24 Hostomice
Czech Republic
o) S
DESIGN:
WEIGHT (kg):
14
EN 15650:2010
FDMC
TPM 083/12
1391
100 - 400
Fire resistance
Fig.
EIS 60
16
EIS 60
17
EIS 60
18
EIS 60
19
EIS 60
20
EIS 60
21