Mandik FDMR Installation, Operation, Maintenance And Service Instructions

Fire damper

Advertisement

Quick Links

TPM 140/19
Version 2023-06-15
FDMR
Fire damper
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
www.mandik.com
MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz

Advertisement

Table of Contents
loading

Summary of Contents for Mandik FDMR

  • Page 1 TPM 140/19 Version 2023-06-15 FDMR Fire damper Technical Documentation Installation, Commissioning, Operation, Maintenance and Service Manual www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...
  • Page 2: Table Of Contents

    TPM 140/19 These technical specifications state a row of manufactured sizes and models of fire dampers FDMR It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL................3 Entry into service and revisions........97 Description..............3 X. ORDERING INFORMATIONS...........99 II.
  • Page 3: General

    FDMR with spring return actuator FDMR with manual control Damper characteristics CE certified acc. to EN 15650 ■...
  • Page 4: Design

    Cables are connected directly to limit switches. ■ ■ with two limit switches signaling of the damper blade Limit switch detail → see page 5 ■ position "CLOSED" and "OPEN". Limit switch Limit switch “CLOSED” “OPEN” Design .80 Page 4 Fire damper - FDMR Version 2023-06-15...
  • Page 5 Class of protection IP 67 CUT-OFF if the arm is moving … connect wire 1+2 ■ Working temperature -25°C … +120°C SWITCH-ON if the arm is moving … connect wire 1+4 ■ Version 2023-06-15 Fire damper - FDMR Page 5...
  • Page 6: Design With Spring Return Actuator

    "OPEN" to the position "CLOSED" takes maximum 20 sec. Signalisation of damper blade position "OPEN" and ■ "CLOSE" is provided by two microswitches. Spring return actuator Thermoelectric activation device BAT Design .40 and .50 Page 6 Fire damper - FDMR Version 2023-06-15...
  • Page 7 1 m, 2 x 0,75 mm² (BFL 2xx-T-ST) with 3-pin plug-in connectors - auxiliary switch cable 1 m, 6 x 0,75 mm² (BFL 2xx-T-ST) with 6-pin plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Version 2023-06-15 Fire damper - FDMR Page 7...
  • Page 8 1 m, 2 x 0,75 mm² (BFN 2xx-T-ST) with 3-pin plug-in connectors - auxiliary switch cable 1 m, 6 x 0,75 mm² (BFN 2xx-T-ST) with 6-pin plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Page 8 Fire damper - FDMR Version 2023-06-15...
  • Page 9 1 m, 2 x 0,75 mm² (BF 2xx-TN-ST) with 3-pin plug-in connectors - auxiliary switch cable 1 m, 6 x 0,75 mm² (BF 2xx-TN-ST) with 6-pin plug-in connectors duct outside temperature +72°C Response temperature thermal fuse duct inside temperature +72°C Version 2023-06-15 Fire damper - FDMR Page 9...
  • Page 10 Max. 95% RH, non-condensing Connection supply Cable 1 m, 2 x 0.5 mm², Betaflam cable heatresistant up to 145°C Duct inside temperature +72 (95/120/140)°C Response temperature thermal fuse Duct outside temperature +72 (95/120/140)°C Page 10 Fire damper - FDMR Version 2023-06-15...
  • Page 11 -20°C … +50°C Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Version 2023-06-15 Fire damper - FDMR Page 11...
  • Page 12: Design With The Communication And Supply Device

    -20°C … +50°C Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Page 12 Fire damper - FDMR Version 2023-06-15...
  • Page 13 -20°C … +50°C Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Version 2023-06-15 Fire damper - FDMR Page 13...
  • Page 14 -20°C … +50°C Non-operating temperature -40°C … +80°C Connection - net cable 0,9 m with EURO plug type 26 - motor 6-pole connector, 3-pole connector - terminal board screw terminals for cable 2x1,5 mm² Page 14 Fire damper - FDMR Version 2023-06-15...
  • Page 15 1 m with EURO plug - motor (BF ...-Top) 4-pole connector - net MP screw terminals 2-pole - actuating mechanism (variable) screw terminals 2-pole - Top-Line PC-Tool (via ZIP-RS232) 3-pole connector Version 2023-06-15 Fire damper - FDMR Page 15...
  • Page 16 Cabel 1m, connected to terminals 1, 2 and 4 - motor Actuator connected on the terminals 2 and 5 - communication and supply device BKN Cabel 1m, connected to terminals 1, 2, 4 and 5 Page 16 Fire damper - FDMR Version 2023-06-15...
  • Page 17: Communication And Control Device Bks 24-1B And Bks 24-9A

    5 VA Protection Class Degree of protection IP 30 Ambient temperature 0°C … +50°C 11-pole connector ZSO-11, it is not part of BKS24-1B, Connection ZSO-11 is 11-pole screw terminal 11 x 1,5 mm Version 2023-06-15 Fire damper - FDMR Page 17...
  • Page 18 Communication and control device BKS 24-9A Nominal voltage AC 24 V 50/60Hz Power consumption 3,5 W Dimensioning 5,5 VA Protection Class Degree of protection IP 30 Ambient temperature 0°C … +50°C Connection terminal 2 x 1,5 mm Page 18 Fire damper - FDMR Version 2023-06-15...
  • Page 19: Dimensions

    TPM 140/19 III. DIMENSIONS SPIRO design with manual control Damper casing Manual control Damper blade Inspection opening cover Sensor sticker Hole for camera Version 2023-06-15 Fire damper - FDMR Page 19...
  • Page 20 TPM 140/19 FLANGE design with manual control Ød Ød1 Ød2 number of holes [mm] [mm] [mm] in the flange Damper casing Manual control Damper blade Inspection opening cover Sensor sticker Hole for camera Page 20 Fire damper - FDMR Version 2023-06-15...
  • Page 21 X=78 mm (BF) * Damper casing Spring return actuator Damper blade Inspection opening cover Thermoelectric activation device BAT Assigment of actuators to individual sizes → see page 24 Hole for camera ■ Version 2023-06-15 Fire damper - FDMR Page 21...
  • Page 22 X=78 mm (BF) * Damper casing Spring return actuator Damper blade Inspection opening cover Thermoelectric activation device BAT Assigment of actuators to individual sizes Hole for camera → see page 24 ■ Page 22 Fire damper - FDMR Version 2023-06-15...
  • Page 23 Values "a" and "c" has to be respected when projecting following air-conditioning duct. Fire damper with installation brackets Weight of the installation bracket is 0,04 kg. ■ Number of installation brackets for individual sizes → see page 24 ■ Version 2023-06-15 Fire damper - FDMR Page 23...
  • Page 24: Technical Parameters

    * Weight of an installation bracket is 0,04 kg. ** Only spiro design SL or SK can be ordered. *** For designs with BKN a weight of 0.5 kg must be added. Page 24 Fire damper - FDMR Version 2023-06-15...
  • Page 25: Installation

    X = recommended min. distance for manual control ≥ 250 mm Y = min. distance for actuator ≥ 200 mm acc. to EN 1366-2 Y = recommended min. distance for manual control ≥ 250 mm Version 2023-06-15 Fire damper - FDMR Page 25...
  • Page 26 100 mm. Outside the wall/ceiling contruction. The duct and ■ Gypsum wall construction with fire classification EI120 ■ damper must be protected by fire insulation. or EI 90, with minimum thickness 100 mm. Page 26 Fire damper - FDMR Version 2023-06-15...
  • Page 27: Statement Of Installations

    Concreting - installation frame R5 Installation frame outside solid EI 90 (h i↔o) S 125 - Aerated ceiling construction Insulation from fire-resistant boards - mortar or gypsum - installation frame R6 concrete Version 2023-06-15 Fire damper - FDMR Page 27...
  • Page 28: In Solid Wall Construction

    ■ EIS 120 - 500 Pa up to diameter DN 315 mm ≥ 100 FDMR Solid wall construction Mortar or gypsum Clamp with threaded rod → see pages 87 to 89 Duct Page 28 Fire damper - FDMR Version 2023-06-15...
  • Page 29 It is possible to install up to 4 dampers symmetrically in one opening ≥ 100 FDMR Solid wall construction Mortar or gypsum Clamp with threaded rod → see pages 87 to 89 Duct Version 2023-06-15 Fire damper - FDMR Page 29...
  • Page 30 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Page 30 Fire damper - FDMR Version 2023-06-15...
  • Page 31 Fire-resistant board - min. th. 15 mm, min. density 870 kg/m (e.g. PROMATECT-H) Screw 4x50 mm - screws must be fixed in the wall construction, use steel anchors if necessary Clamp with threaded rod → see pages 87 to 89 Duct Version 2023-06-15 Fire damper - FDMR Page 31...
  • Page 32 Installation is limited to DN 200 mm diameter ■ ≥ 100 FDMR Solid wall construction Fire-resistant foam HILTI CFS-F FX Stucco plaster Clamp with threaded rod → see pages 87 to 89 Duct Page 32 Fire damper - FDMR Version 2023-06-15...
  • Page 33 (e.g. Promat K84 or equivalent) to the construction and damper casing ≥ 100 ⑤ ≥ 150 FDMR Solid wall construction Solid ceiling construction Mortar or gypsum Mineral wool board - min. density 140 kg/m (e.g. PROMAPYR-T150, ROCKWOOL HARDROCK / STEPROCK HD) Duct Version 2023-06-15 Fire damper - FDMR Page 33...
  • Page 34 → see page 90 ■ Conditions of this installation are also valid for the installation in Solid ceiling construction ■ ≥ 100 FDMR Solid wall construction Solid ceiling construction Mortar or gypsum Duct Page 34 Fire damper - FDMR Version 2023-06-15...
  • Page 35: Installation Outside Solid Wall Constrution

    Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm ISOVER Protect BSK glue - apply on the insulation and fix it to the fire separation construction Clamp with threaded rod → see pages 87 to 89 Version 2023-06-15 Fire damper - FDMR Page 35...
  • Page 36 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Page 36 Fire damper - FDMR Version 2023-06-15...
  • Page 37 11 ROCKWOOL Firepro glue - apply on the insulation and fix it to the fire Screw 4x50 mm - screws must be fixed in the wall construction, use steel separation construction anchors if necessary 12 Clamp with threaded rod → see pages 87 to 89 Version 2023-06-15 Fire damper - FDMR Page 37...
  • Page 38: In Gypsum Wall Construction

    ■ EIS 120 - 500 Pa up to diameter DN 315 mm ≥ 100 FDMR Gypsum wall construction Mortar or gypsum Clamp with threaded rod → see pages 87 to 89 Duct Page 38 Fire damper - FDMR Version 2023-06-15...
  • Page 39 It is possible to install up to 4 dampers symmetrically in one opening ≥ 100 FDMR Gypsum wall construction Mortar or gypsum Clamp with threaded rod → see pages 87 to 89 Duct Version 2023-06-15 Fire damper - FDMR Page 39...
  • Page 40 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Page 40 Fire damper - FDMR Version 2023-06-15...
  • Page 41 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Version 2023-06-15 Fire damper - FDMR Page 41...
  • Page 42 Fire-resistant board - min. th. 15 mm, min. density 870 kg/m (e.g. PROMATECT-H) Screw 4x50 mm - screws must be fixed in the wall construction, use steel anchors if necessary Clamp with threaded rod → see pages 87 to 89 Duct Page 42 Fire damper - FDMR Version 2023-06-15...
  • Page 43: Fdmr

    Installation is limited to DN 200 mm diameter ■ ≥ 100 FDMR Gypsum wall construction Fire-resistant foam HILTI CFS-F FX Stucco plaster Clamp with threaded rod → see pages 87 to 89 Duct Version 2023-06-15 Fire damper - FDMR Page 43...
  • Page 44 (e.g. Promat K84 or equivalent) to the construction and damper casing ≥ 100 ⑤ ≥ 150 FDMR Gypsum wall construction Solid ceiling construction Mortar or gypsum Mineral wool board - min. density 140 kg/m (e.g. PROMAPYR-T150, ROCKWOOL HARDROCK / STEPROCK HD) Duct Page 44 Fire damper - FDMR Version 2023-06-15...
  • Page 45 → see page 90 ■ Conditions of this installation are also valid for the installation in Solid ceiling construction ■ ≥ 100 FDMR Gypsum wall construction Solid ceiling construction Mortar or gypsum Duct Version 2023-06-15 Fire damper - FDMR Page 45...
  • Page 46: Installation Outside Gypsum Wall Constrution

    Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm ISOVER Protect BSK glue - apply on the insulation and fix it to the fire separation construction Clamp with threaded rod → see pages 87 to 89 Page 46 Fire damper - FDMR Version 2023-06-15...
  • Page 47: Weichschott System Hilti

    Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Version 2023-06-15 Fire damper - FDMR Page 47...
  • Page 48 11 ROCKWOOL Firepro glue - apply on the insulation and fix it to the fire Screw 4x50 mm - screws must be fixed in the wall construction, use steel separation construction anchors if necessary 12 Clamp with threaded rod → see pages 87 to 89 Page 48 Fire damper - FDMR Version 2023-06-15...
  • Page 49: Installation In Sandwich Wall Construction

    Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Version 2023-06-15 Fire damper - FDMR Page 49...
  • Page 50: Shaft Walls

    Assembly without support structure Rigips solution is shown here as an example. Alternatively it is possible to apply the ■ solution from Knauf or Promat. In such a case follow the instructions of the producer. Page 50 Fire damper - FDMR Version 2023-06-15...
  • Page 51 Fire-resistant board th. 20 mm Rigips Glasroc F Ridurit Steel U-profile Rigips R-UW 50 or Rigips R-CW 50 Screw Rigips Ridurit TX 3,5x35 mm Additional fire-resistant board tl. 20 mm Rigips Glasroc F Ridurit Version 2023-06-15 Fire damper - FDMR Page 51...
  • Page 52 All technical specifications and conditions can be found at www.rigips.cz ■ ■ Installation frame can be installed on the damper or delivered separately Installation procedure of the installation frame for FDMR → see manual ■ For more R1 frame details → see page 62 ■...
  • Page 53: In Solid Ceiling Construction

    Clamp with threaded rod → see pages 87 to 89 min. 125 mm - Aerated concrete - for EIS 90 and EIS 120 Duct min. 150 mm - Concrete - for EIS 120 Version 2023-06-15 Fire damper - FDMR Page 53...
  • Page 54 Ø Ø FDMR Solid ceiling construction Mortar or gypsum Clamp with threaded rod → see pages 87 to 89 * min. 110 mm - Conrete Duct min. 125 mm - Aerated concrete Page 54 Fire damper - FDMR Version 2023-06-15...
  • Page 55 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of penetration and damper casing Version 2023-06-15 Fire damper - FDMR Page 55...
  • Page 56 Fire-resistant board - min. th. 15 mm, min. density 870 kg/m (e.g. PROMATECT-H) Screw 4x50 mm - screws must be fixed in the wall construction, use steel anchors if necessary Clamp with threaded rod → see pages 87 to 89 Duct Page 56 Fire damper - FDMR Version 2023-06-15...
  • Page 57: Installation Outside Solid Ceiling Constrution

    Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm ISOVER Protect BSK glue - apply on the insulation and fix it to the fire separation construction Clamp with threaded rod → see pages 87 to 89 Version 2023-06-15 Fire damper - FDMR Page 57...
  • Page 58 Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm ISOVER Protect BSK glue - apply on the insulation and fix it to the fire separation construction Clamp with threaded rod → see pages 87 to 89 Page 58 Fire damper - FDMR Version 2023-06-15...
  • Page 59 Duct penetration insulation collar - th. 60 mm (System ROCKWOOL Clamp with threaded rod → see pages 87 to 89 Wired Mat 105 Alu) - glued (pos. 8) and fixed with screws to the wall construction Version 2023-06-15 Fire damper - FDMR Page 59...
  • Page 60 Rebar - steel rod Ø 6 mm, mesh hole 100 mm Standard air duct, made of galvanized sheet metal min. thickness 0,8 mm Clamp with threaded rod → see pages 87 to 89 Page 60 Fire damper - FDMR Version 2023-06-15...
  • Page 61: Installation Frames

    Installation frame R3 Installation frame R4 Installation frame R5 (DN 100-200) Installation frame R5 (DN 225-800) Installation frame R6 Installation frame R7 ■ Installation frame can be installed on the damper or delivered separately Version 2023-06-15 Fire damper - FDMR Page 61...
  • Page 62: Installation Frame R1, R2

    Installation frame R2 - solid wall/gypsum wall th. 150 mm or solid ceiling th. 150 mm Material: ■ Installation frame - cement-lime boards ■ Fasteners - galvanized steel ■ Installation frame R1 Installation frame R2 Page 62 Fire damper - FDMR Version 2023-06-15...
  • Page 63 For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R1 - wall th. 100 mm Installation frame R2 - wall th.
  • Page 64 → see page 90 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ It is possible to install up to 4 dampers symmetrically in one opening ■...
  • Page 65 → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R1 - solid wall th. 100 mm or solid ceiling th. 110 mm Installation frame R2 - solid wall th.
  • Page 66 → see page 90 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R1 - wall th. 100 mm Installation frame R2 - wall th. 150 mm ■...
  • Page 67 → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ It is possible to install up to 4 dampers symmetrically in one opening ■...
  • Page 68 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R1 - gypsum wall th. 100 mm or solid ceiling th. 110 mm Installation frame R2 - gypsum wall th.
  • Page 69 For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R1 - ceiling th. 110 mm** Installation frame R2 - ceiling th.
  • Page 70 → see page 90 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ It is possible to install up to 4 dampers symmetrically in one opening ■...
  • Page 71: Installation Frame R3, R4

    Installation frame R4 - solid wall th. 150 mm or solid ceiling th. 150 mm Material: ■ Installation frame - cement-lime boards ■ Fasteners - galvanized steel ■ Installation frame R3 Installation frame R4 Version 2023-06-15 Fire damper - FDMR Page 71...
  • Page 72 For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R3 - wall th. 100 mm Installation frame R4 - wall th.
  • Page 73 For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Installation frame R3 - ceiling th. 110 mm** Installation frame R4 - ceiling th.
  • Page 74: Installation Frame R5

    Installation frame R5 for dampers from ØD 225 mm is with sheet metal reinforcements ■ Material: ■ Installation frame - cement-lime boards ■ Fasteners - galvanized steel ■ Installation frame R5 ( D 100-200) Installation frame R5 ( D 225-800) Ø Ø Page 74 Fire damper - FDMR Version 2023-06-15...
  • Page 75 ■ For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ ≥ 100 FDMR Installation frame - apply HILTI CFS-S ACR mastic at the entire area and...
  • Page 76 → see page 90 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Conditions of this installation are also valid for the installation in Solid ceiling construction ■...
  • Page 77 ■ For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ ≥ 100 FDMR Installation frame - apply HILTI CFS-S ACR mastic at the entire area and...
  • Page 78 → see page 90 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Conditions of this installation are also valid for the installation in Solid ceiling construction ■...
  • Page 79 For connection of following duct → see page 90 Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ FDMR Installation frame - apply HILTI CFS-S ACR mastic at the entire area and...
  • Page 80 Adjacent duct must be suspended or supported, as required by the duct suppliers Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ FDMR...
  • Page 81: Installation Frame R6

    Installation frame is equipped with an intumescent sealing on the inside. This sealing fills the gap between the damper casing and frame in the event of a fire Material: ■ Installation frame - cement-lime boards ■ Fasteners - galvanized steel ■ Installation frame R6 D+90 Ø D+170 Ø Version 2023-06-15 Fire damper - FDMR Page 81...
  • Page 82 Adjacent duct must be suspended or supported, as required by the duct suppliers Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Additional board of duct ≤...
  • Page 83 ■ Adjacent duct must be suspended or supported, as required by the duct suppliers Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ 40…150 Additional board of frame Additional board of duct ≤...
  • Page 84: Installation Frame R7

    Position of the damper can be directly on the ceiling or at a distance of max. 80 mm from the ceiling ■ Material: ■ Installation frame - cement-lime boards ■ Fasteners - galvanized steel ■ Installation frame R7 D+170 Ø D+276 Ø (from promaseal) Page 84 Fire damper - FDMR Version 2023-06-15...
  • Page 85 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Gypsum construction must be made in accordance with the specifications of the wall system manufacturer ■...
  • Page 86 ■ Installation frame can be installed on the damper or delivered separately ■ Installation procedure of the installation frame for FDMR → see manual ■ Gypsum construction must be made in accordance with the specifications of the wall system manufacturer ■...
  • Page 87: Suspension Systems

    Washer for M8 - M20 Coupling Nut M8 - M20 Anchor Hinge plate - min. thickness 10 mm Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Version 2023-06-15 Fire damper - FDMR Page 87...
  • Page 88 TPM 140/19 Example of fixing FDMR to the wall or ceiling In solid wall construction In solid ceiling construcion In gypsum wall construction Ø100–400 Ø450–800 t(mm): 1,5 t(mm): 2,5 Ø100–400 Quick closing system 2x screw M6×20. Fixing nut for threaded rod M8.
  • Page 89 TPM 140/19 Example of fixing FDMR outside the wall or ceiling Outside solid wall construction Outside solid ceiling construcion Outside gypsum wall construction Ø100–400 Ø450–800 t(mm): 1,5 t(mm): 2,5 Ø100–400 Quick closing system 2x screw M6×20. Fixing nut for threaded rod M8.
  • Page 90: Example Of Duct Connection

    Duct Extension piece (if required) Damping pad Bolt assembly M8 (bolt M8x20 mm, 2 pcs large washer M8, nut M8) Electrically conductive connection of the damping pad with extension piece and duct Page 90 Fire damper - FDMR Version 2023-06-15...
  • Page 91: Technical Data

    Determination of pressure loss by using diagram ρ = 1,2 kg/m Coefficient of local pressure loss ξ 2,736 2,099 1,781 1,527 1,272 0,929 0,636 0,892 0,747 0,627 0,576 ξ 0,531 0,471 0,455 0,393 0,344 0,307 0,273 0,258 0,243 0,111 0,099 Version 2023-06-15 Fire damper - FDMR Page 91...
  • Page 92: Noise Data

    -16,7 -24,1 -33,2 -5,2 -3,9 -4,3 -6,4 -10,1 -15,6 -22,7 -31,5 -5,5 -4,1 -5,9 -9,4 -14,6 -21,5 -5,9 -4,1 -5,6 -8,9 -13,8 -20,4 -28,8 -6,2 -4,3 -3,9 -5,3 -8,4 -13,1 -19,5 -27,6 Page 92 Fire damper - FDMR Version 2023-06-15...
  • Page 93: Material, Finishing

    The damper blade in the variant for chemical environments (Class A4) is always treated with a coating of chemically resistant Promat SR. Any other requirements for the design will be considered atypical and will be addressed on an individual basis. Version 2023-06-15 Fire damper - FDMR Page 93...
  • Page 94: Transportation, Storage And Warranty

    The warranty for fire dampers FDMR, provided by the ■ If the dampers are damaged by transport, a record must manufacturer, is completely void if actuating, closing and ■...
  • Page 95: Assembly, Attendance And Maintenance

    Protection of the damper casing against buckling during installation, especially for DN over 400 mm! WRONG! Brace with wooden blocks Brace with wedges Version 2023-06-15 Fire damper - FDMR Page 95...
  • Page 96 DN 350 - DN 800 Damper Mounting plate Sealing cover Sealing of a mounting plate Cover of mounting plate Thermal fuse Manual control Spring return actuator Thermoelectric activation device BAT 10 Sensor sticker Page 96 Fire damper - FDMR Version 2023-06-15...
  • Page 97: Entry Into Service And Revisions

    Removing the thermal fuse from the fuse holder of a manual control, checks its correct functionality. ■ The manual control is identified as M1 to M5, depending on the closing spring strength. ■ Version 2023-06-15 Fire damper - FDMR Page 97...
  • Page 98 If the thermal fuse Tf2 is interrupted (due to temperature inside the duct) , only the spare part ZBAT 72 (95/120/140) needs ■ to be replaced (acc.to the activation temperature). → see page 10 Page 98 Fire damper - FDMR Version 2023-06-15...
  • Page 99: Ordering Informations

    SL - spiro damper with rubber sealing SK - spiro damper with rubber sealing and installation brackets EXAMPLE: FDMR SL 200 .40 - SL - spiro damper with rubber sealing, 200 - damper diameter, .40 - design Damper design Additional digit...
  • Page 100: Data Label

    Data label is placed on the damper casing (example) ■ MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: DESIGN: WEIGHT (kg): SERIAL.NO.: MANUAL CLASSIFICATION: Cert. No.: 1391-CPR-XXXX/XXXX, DoP: PM/XXXX/XX/XX/X TPM XXX/XX EN 15650:2010 Page 100 Fire damper - FDMR Version 2023-06-15...
  • Page 101 The producer reserves the right for innovations of the product. For actual product information see www.mandik.com www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...