Mandik FDMC General Information Manual page 18

Hide thumbs Also See for FDMC:
Table of Contents

Advertisement

Fig.. 22
Gypsum wall construction - installation next to wall, ceiling - mortar or gypsum and mineral wool
A
1 2
3
10 to 50
3
2
1
A
B
1 2
10 to 50
2
1
B
POSITION:
1
Fire damper FDMC
2
Mortar or gypsum
3
Mineral stone wool min. density 140 kg/m
D-20
2 1
3
2 1
Notice:
Gap between damper and construction is filled by mortar or
gypsum and mineral wool
Wool is fixed to damper body and construction by fire protection
mastic.
Mineral wool thickness = construction thickness + 50 mm
Damper axis has to be horizontal
Installation is valid for ceiling construction
3
17
A-A
3
2
3
2
≥ 100
(≥ 100)+50
B-B
2
2
≥ 100
TPM 083/12
EIS 60
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.