6.3 Analog Output

This section shows how analog output can be configured. The following figure is
an example for analog input AO1. The configuration for EAO is similar to AO1,
only with different parameters shown in the table below.
Fig. 6-3: Example with analog output AO1
Code
Name
E2.25 AO1 output mode
E2.27 AO1 gain setting
Pressure command corre-
F2.04
sponding to 10V or 20mA
Pressure feedback corre-
F2.06
sponding to 10V or 20mA
Flow command correspond-
F2.08
ing to 10V or 20mA
AO1 output
F2.31
(use E2.27 for gain)
EAO output
F2.32
(use H8.27 for gain)
DOK-RCON03-FCP5020****-QU02-EN-P
Setting Range
0: 0...10 V
1: 0...20 mA
0.00...10.00
0.1...1,000.0 bar
0.1...1,000.0 bar
1...5,000 rpm
0: No function assigned from ASF
1: Pressure command (scaled by
F2.04)
2: Pressure feedback (scaled by
F2.06)
3: Setting speed (include direc-
tion) (scaled by F2.08)
4: Output speed (include direc-
tion) (scaled by F2.08)
Bosch Rexroth AG
Electric Connection
Default
Min.
Attri.
1
-
Run
1.00
0.00
Run
10.0
0.1
Stop
100.0
0.1
Stop
400
1
Stop
0
-
Run
0
-
Run