Bosch Rexroth Sytronix FcP 5020 Quick Start Manual page 16

Frequency-controlled pump drive system
Hide thumbs Also See for Rexroth Sytronix FcP 5020:
Table of Contents

Advertisement

Bosch Rexroth AG
Electric Connection
Code
Name
Pressure feedback corre-
F2.06
sponding to 10V or 20mA
Pressure feedback null off-
F2.07
set in V or mA
Flow command correspond-
F2.08
ing to 10V or 20mA
Flow command null offset in
F2.09
V or mA
Tab. 6-1: Analog input parameter list
As the default FcP 5020 configuration, analog input AI2 [F2.01 = 2] is configured
as the pressure feedback input. Analog input AI1 or EAI1 has no preassigned
configuration by the FcP 5020.
For broken wire protection of analog input, please check the following table for
setting range of E1.61. For more information please refer to EFC 5610 converter
document (R912005856 or R912005854).
Code
Name
E1.61 Broken wire protection
Tab. 6-2: Parameter E1.61 for broken wire protection
Wire broken monitoring function for all analog inputs can be activa-
ted by E1.61. Default value of E1.61 has been set to 0 in FcP 5020
and 2 in CytroPac default setting.
12/75
Setting Range
0.1...1,000.0 bar
0.0...5.0 V, mA
1...5,000 rpm
0.0...5.0 V, mA
Setting Range
0: Inactive
1: Warning
2: Error
Default
Min.
100.0
0.1
4.0
0.1
(mA)
400
1
0.0
0.1
Default
Min.
0
-
DOK-RCON03-FCP5020****-QU02-EN-P
FcP 5020
Attri.
Stop
Stop
Stop
Stop
Attri.
Stop