o Humidity High Level Alarm: Set the maximum allowed humidity level above which an
alarm is sent. The alarm ceases when the humidity drops below this level. If the user
acknowledges the alarm, the alarm messages temporarily cease (for the reminder time).
o Ammonia High Level: Set the ammonia level at which an alarm is sent.
o Enable Secondary Alarms: Refer to Prioritizing Alarms, page 65.
o Enable potentiometer alarms, which send an alarm when vent/curtain potentiometer
controlled devices fail. To enable, sent the time frame. If the from/to times are set to
0:00 (default) the alarm is disabled.
4.4.2 P
A
RIORITIZING
Platinum Touch/Rotem One Touch enables prioritizing alarms. When enabled:
ventilation-related alarms are defined as critical. The main alarm relay will transmit these
•
alarms to the device wired to the relay (for example, a dialer).
non-ventilation alarms are defined as non-critical. A secondary relay will transmit alarms to
•
another device (for example, an ELS).
To prioritize alarms:
1. Go to System > Relay Layout.
2. Define a relay as Alarm (N.C.).
3. Go to Manage > Alarm Setting > Help
4. Enable Advanced Alarms.
5. Go to Manage > Alarm Setting.
6. Scroll to Secondary Alarms and define as Yes.
Humidity Sensor Alarm
Ammonia Alarm
Secondary Alarms
Potentiometer Alarm