2. Allgemeine Informationen
Description
2 .5. Te ch n ic al d at a - brin e a ppl ic at io n
Heat pump type
Model
Space heating energy effi ciency class
Performance data acc. to EN 14511 brine application at nominal speed
Heat output at B0°C/W35°C
Power intake at B0°C/W35°C
COP at B0°C/W35°C
Application with process reversal at nominal speed
Cooling capacity at B15°C/W18°C
Power intake at B15°C/W18°C
EER at B15°C/W18°C
Cooling capacity at B15°C/W7°C
Power intake at B15°C/W7°C
EER at B15°C/W7°C
Sound emission according to EN 12102
Sound power level nominal
Sound power level maximum
Dimensions
Height / Width / Depth
Weight HGL / HGL P
Minimum size of installation room
Flat collector set
Number of pipe circuits for the fl at collector
Total pipe length at 7 kW / 10 kW / 13 kW
Distributor length
Brine mixture
8
1)
Installation instructions TERRA SWM
TERRA SWM 3-13
HGL
HGL P
A++
A++
35°C / 55°C
Unit
kW
6.60
kW
1.32
-
5.01
kW
11.12
kW
1.18
-
9.38
kW
7.44
kW
0.96
-
7.78
dB(A)
41
dB(A)
47
mm
1262 / 620 / 762
kg
170 / 175
6.82
-
4 / 5 / 6
m
400 / 500 / 600
mm
240 / 300 / 360
l
140 / 175 / 210
(C) IDM ENERGIESYSTEME GMBH