CONTROL SOLUTIONS LogTag VFC400-WiFi Product User Manual page 11

Wireless vaccine temperature monitoring data logger
Hide thumbs Also See for LogTag VFC400-WiFi:
Table of Contents

Advertisement

Preparing a VFC400-WiFi for first use
VFC400-WiFi Start Options
During configuration with Control Solutions VTMC you can decide when the VFC400-WiFi starts taking
temperature readings:
Push button start
The logger will start taking temperature readings as soon as you have pressed the
(see
Starting the Logger on
When you choose the push button start option, you can select to record
after a
delay:
If you select
pre-start
l
continue to do so until you start the unit. No alarms are processed while pre-start readings are being
taken, pre-start readings will not appear in the PDF file, and no PDF file will be generated. Using pre-start
readings is a good way to avoid data loss if you forget to start the unit, as you can still access the data
using Control Solutions VTMC.
If you configure the VFC400-WiFi to start after a delay period, the logger will not immediately record
l
temperature readings after you have pressed
and record readings only after the timer has ended. The value for the timer is set during configuration. If
enabled, it will continue to take pre-start readings.
Date/Time start
The logger will start taking temperature readings at the date and time you specify (local time). You cannot
combine a date/time start with pre-start readings or the start delay function.
Alarm Configuration Options
The VFC400-WiFi can display an alarm if either of the configured alarm trigger conditions have been met. This
is indicated on the display by showing the Alarm Indicator ( ) and the Day Alarm Marker for
today (
). Additionally, the red LED will blink every 4 seconds.
If an alarm is triggered, a notification is also sent immediately to your LogTag
Each alarm trigger condition consists of a threshold temperature value, an activation type (which can be
instant, consecutive or accumulative
If an alarm trigger condition requires readings to exceed an upper threshold temperature it is called an upper
alarm. If an alarm trigger condition requires readings to go below a lower threshold it is called a lower alarm.
All alarm trigger conditions are configured in the Alarm Settings tab during configuration of the logger with
Control Solutions VTMC.
The screen shows an example where:
1
Instant = one temperature reading is above (below) the threshold
l
Consecutive = temperature readings are above (below) the threshold for the time defined in the activation delay without interruption
l
Accumulative = temperature readings are above (below) the threshold for the total time defined in the activation delay time, but may not necessarily
l
be sequential
VFC400-WiFi User Guide
page 29).
readings, the VFC400-WiFi starts recording as soon as it is configured and will
START
1
) and a delay time, if it is not an instant alarm.
START
Pre-start readings
, but start a countdown timer instead,
/CLEAR/STOP
®
Online account.
11
button
/CLEAR/STOP
or
Begin recording

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LogTag VFC400-WiFi and is the answer not in the manual?

Table of Contents