EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

ENGINEERING, COMMISSIONING

Please refer also to CentraLine NX BACnet Utilities Driver -
User Guide (Product Literature No.: EN2Z-1020GE51) for
detailed information.

Required Preparations

In order to access (with a laptop or PC) the EAGLEHAWK NX
controller via Ethernet/IP for the first time, the default pass-
words are used. For IP connections, you may employ any one
of the following two options:
Option 1: USB 2.0 Device (recommended)
This USB 2.0 Device interface is the recommended interface
for downloading applications and firmware via COACH NX.
An "A-Male to B-Male" USB cable is required.
Fig. 32. A-male to B-male USB cable
For access via USB, the EAGLEHAWK NX controller has a
permanent default IP address 192.168.255.241. Your PC's IP
address must match the EAGLEHAWK NX controller's default
IP address subnet: We recommend using DHCP or "Obtain
an automatic IP address".
Option 2: Standard Ethernet Interface
The default IP address of Ethernet interface 1 is:
192.168.200.20
and the default IP address of Ethernet interface 2 is:
192.168.201.20
In any case, your PC's IP address must match the
EAGLEHAWK NX controller's default IP address subnet
(255.255.255.0).

Behavior of Outputs during Download

Table 17. Behavior of outputs during firmware download /
application download
analog, binary,
output behavior
and floating
during firmware
outputs
download
As soon as "receive
heartbeat" (the value
outputs of Panel
of which CANNOT
I/O modules
be altered using
(CLIOP82x)
COACH NX) expires,
outputs go to safety
position.
As soon as "receive
heartbeat" (the value
outputs of
of which can be
L
W
I/O
ON
ORKS
altered using
modules
COACH NX) expires,
(CLIOL82x)
outputs go to safety
position.
After the configured
onboard I/Os
time-out, go to safety
position.
NOTE: These behaviors were determined using a test
application with a cycle time of 10 seconds. A value
update was triggered every 10 seconds.
29
output behavior
during application
download
As soon as "receive
heartbeat" (the value
of which CANNOT
be altered using
COACH NX) expires,
outputs go to safety
position.
As soon as "receive
heartbeat" (the value
of which can be
altered using
COACH NX) expires,
outputs go to safety
position.
After the configured
time-out, go to safety
position.
EN1Z-1039GE51 R1218