EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Powering Field Devices and Panel Bus I/O Module via Separate
Transformers
24 V actuator connected to, e.g., an analog output module
Field device located 100 ... 400 m from the analog output
module
F1
CLIOP822A
24 VAC
73
Y (0...10 Vdc)
230 VAC
74
1...8
24 V0
11...18
Fig. 25. Power supply via a separate transformer
Powering Field Devices via Panel Bus I/O Module
24 V actuator connected to, e.g., an analog output module
Field device located max. 100 m from the analog output
module
F2
F1
CLIOP822A
24 VAC
73
230 VAC
74
1...8
24 V0
11...18
Fig. 26. Power supply via Panel Bus I/O Module
24 V0
230 VAC
24 VAC
F2
24 VAC
Y
GND
max. 400 m
24 VAC
Y (0...10 Vdc)
Y
GND
max. 100 m
23
EN1Z-1039GE51 R1218