EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
2
1
24 25 26
~
1
2
24Vac
!
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired
within the same block.
Fig. 28. CLNXxxx26xxx connection example (with two XS830 Auxiliary Terminal Packages)
The XS830 and XS831 Auxiliary Terminal Packages are optional accessories which can be mounted onto the top and/or bottom
of the EAGLEHAWK NX controller in order to equip them with additional terminals for the connection of, e.g., shields, sensors,
GND, N, 230 V, or 24 V (but not earth!).
NOTE: Use a min. distance of 10 cm between power cables and 0...10 V / sensor cables in order to prevent signal
disturbances on the 0...10 V / sensor cables.
1
A1 A2 A3 A4 A5 A6 A7
1 2 3 4 5 6 7
27 28 29 30 31 32
33 34 35 36
CLNXEH26ND100A
BLOCK 1
BLOCK 1
3
4
5
6
7
8
9 10
A1 A2 A3 A4 A5 A6 A7
1 2 3 4 5 6 7
L N
ACTIVE SENSOR
1: GND (24V 0)
~
2: 24V POWER
~
3: 0...10 VDC
2
3
40
B1 B2 B3 B4 B5 B6 B7
XS830
1 2 3 4 5 6 7
37
38 39
40 41 42 43 44 45 46 47
BLOCK 2
BLOCK 2
11 12 13 14 15 16 17 18
B1 B2 B3 B4 B5 B6 B7
XS830
1 2 3 4 5 6 7
14
FAN
FAN
1
2
1: 230V N
1: 230V N
2:
230V~
2:
230V~
M
25
DRY
CONTACT
1: GND
2: SIGNAL
1
2
33
19
20
21
22
23
15
FAN
1
2
1
2
1: 230V N
2:
230V~
M
M
EN1Z-1039GE51 R1218